Installation Manual

NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[90 of 149]
101. Type the name of the unit (4 characters maximum) that
the above alarms are measured in (ex. volt, amp, etc.),
then press
ENTER
.
102. The system responds with...
Off Delay Time: current info
Off Delay Time:
103. Type the required alarm off delay time period* and a
modifier*, then press
ENTER
. The off delay time is the
amount of seconds that an alarm condition must cease
before the system recognizes that the alarm condition
ceased.
* Enter a valid value (0-9999) then the modifier (s for
seconds, m for minutes, h for hours). If no modifier
entered, modifier defaults to seconds.
104. The system responds with...
On Delay Time: current info
On Delay Time:
105. Type the required alarm on delay time period* and a
modifier*, then press
ENTER
. The on delay time is the
amount of seconds that an alarm condition must exist
before the system recognizes it as an alarm condition.
* Enter a valid value (0-9999) then the modifier (s for
seconds, m for minutes, h for hours). If no modifier
entered, modifier defaults to seconds.
106. The system responds with...
Save changes (Y or N):
107. Type
Y
if the above entered data is to be saved in the
current analog channel configuration and
N
if not, then
press
ENTER
.
108. The system will display the second analog channel
configuration. Enter the required data for each analog
channel as described above until the system displays the
default configuration of the first binary channel.
Configuring Binary Channels
Refer to the worksheets (or copies of) located at the end of
"Installing LMS1000" as a guide in programming the various
channels associated with the system.
Note:
This information can also be programmed through the
command CONFIG B_ which is described later in this section.
Note:
Parameters which apply only to TL1 commands/messages do
not appear for configuration if the TL1 software option is not
installed.
Note:
The "Alarm Condition" attribute of the MCA Interface channels
is not configurable. The Operation section in the User
Instructions (Section 5847) lists the MCA Interface channels.
Section 5847 can be accessed via the CD (Electronic
Documentation Package) furnished with your system.
1. After the system responds with the first binary channel
default configuration, the following is displayed...
Channel active (Y or N):
2. Type
Y
if the channel is required to be active and
N
if not,
then press
ENTER
.
3. If ”N” was entered, the system displays another binary
channel configuration. If ”Y” was entered, the system
allows the default configuration information of the
current binary channel to be changed as shown below.
4. The system will respond with...
Name: current info
Name:
5. Type the desired name for this binary channel (30
characters maximum), then press
ENTER
.
6. The system responds with...
Sub-access Identifier: current info
Sub-access Identifier:
7. This parameter applies only to TL1 commands/messages.
Type the name (20 characters maximum) of the sub-
access identifier that this channel belongs to, then press
ENTER
. The group of LMS1000 channels monitoring a
sub-entity in an NMA system should have the same
access identifier and sub-access identifier. Only alpha-
numeric characters can be entered for this parameter.
TL1 uses specific values for this parameter. Refer to
TA-NWT-001360, Table 4-1.
8. The system responds with...
System Alarm Report mode: current info
System Alarm Report mode (Y or N):
9. Type
Y
if the system is required to initiate an alarm report
if the alarm condition occurs on this channel and
N
if not,
then press
ENTER
.
10. The system responds with...
Condition Type: current info
Condition Type:
11. This parameter applies only to TL1 commands/messages.
Type the name (20 characters maximum) which
describes this alarm or event state, then press
ENTER
.
Only alpha characters can be entered for this parameter.
TL1 uses specific values for this parameter. Refer to