Installation Manual

NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[87 of 149]
27. 27) Type ‘N’ for ‘Normal’ operation.
Type ‘G’ for ‘Global’ command operation
Then press <ENTER>
28. The system responds with...
Limit 1 Enabled: current info
Limit 1 Enabled (Y or N):
29. Type
Y
to enable this alarm limit or
N
to disable this alarm
limit. Then press
ENTER
.
30. The system responds with...
Limit 1 Value: current info
Limit 1 Value:
31. Type the required value of the first alarm setting (5 digits,
20000 maximum), then press
ENTER
.
32. The system responds with...
Limit 1 Type: current info
Limit 1 Type is High or Low (H or L):
33. Type
H
if the first alarm setting is a high limit and
L
if the
first alarm setting is a low limit, then press
ENTER
.
34. The system responds with...
Limit 1 Name: current info
Limit 1 Name:
35. Type the desired name of the first alarm setting (10
characters maximum), then press
ENTER
.
36. The system responds with...
Limit 1 Notification Code: current info
Limit 1 Notification Code:
37. This parameter applies only to TL1 commands/messages.
Type one of the following codes which describes the
severity of this alarm or event condition, then press
ENTER
.
CR - critical alarm NA - not alarmed
MJ - major alarm NR - not reported when event occurs
MN - minor alarm
38. The system responds with...
Limit 1 Service Effect Code: current
info
Limit 1 Service Effect Code:
39. This parameter applies only to TL1 commands/messages.
Type one of the following codes which describes how this
alarm or event affects service, then press
ENTER
.
SA = service-affecting condition, immediate action
required
NSA = nonservice-affecting condition, action required
40. The system responds with...
Alarm Class Number:
41. Type the desired alarm class number associated with the
first alarm limit, then press
ENTER
. Alarm classes are
specified with the numbers 0 through 8, with 0
representing no alarm class.
42. The system responds with...
Condition Type: current info
Condition Type:
43. This parameter applies only to TL1 commands/messages.
Type the name (20 characters maximum) which
describes this alarm or event state, then press
ENTER
.
Only alpha characters can be entered for this parameter.
TL1 uses specific values for this parameter. Refer to
TA-NWT-001360 Tables 5-1 through 5-4.
44. The system responds with...
Condition Description: current info
Condition Description:
45. This parameter applies only to TL1 commands/messages.
Type a user-defined text message (40 characters
maximum) which provides a detailed description of this
alarm, event, or condition. Then press
ENTER
. May also
be used to describe any action to be taken as a result of
the condition. All printable ASCII characters are valid
except for the percent sign (%), double quotes ("), and the
backslash (\).
46. The system responds with...
Limit 2 Enabled: current info
Limit 2 Enabled (Y or N):
47. Type
Y
to enable this alarm limit or
N
to disable this alarm
limit. Then press
ENTER
.
48. The system responds with...
Limit 2 Value: current info
Limit 2 Value:
49. Type the required value of the second alarm setting (5
digits, 20000 maximum), then press
ENTER
.
50. The system responds with...
Limit 2 Type: current info
Limit 2 Type is High or Low (H or L):
51. Type
H
if the second alarm setting is a high limit and
L
if
the second alarm setting is a low limit, then press
ENTER
.
52. The system responds with...
Limit 2 Name: current info
Limit 2 Name:
53. Type the desired name of the second alarm setting (10
characters maximum), then press
ENTER
.
54. The system responds with...