Installation Manual

NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[86 of 149]
2. Type
Y
if the channel is required to be active and
N
if not,
then press
ENTER
.
3. If ”N” was entered, the system displays another analog
channel configuration. If ”Y” was entered, the system
allows the default configuration information of the
current analog channel to be changed as shown below.
4. The system responds with...
Name: current info
Name:
5. Type the desired name for this analog channel (30
characters maximum), then press
ENTER
.
6. The system responds with...
Sub-access Identifier: current info
Sub-access Identifier:
7. This parameter applies only to TL1 commands/messages.
Type the name (20 characters maximum) of the sub-
access identifier that this channel belongs to, then press
ENTER
. The group of LMS1000 channels monitoring a
sub-entity in an NMA system should have the same
access identifier and sub-access identifier. Only alpha-
numeric characters can be entered for this parameter.
TL1 uses specific values for this parameter. Refer to
TA-NWT-001360, Table 4-1.
8. The system responds with...
System Alarm Report mode: current info
System Alarm Report mode (Y or N):
9. Type
Y
if the system is required to initiate an alarm report
if an alarm limit is exceeded on this channel and
N
if not,
then press
ENTER
.
10. The system responds with...
Transducer Type: current info
Transducer Type (Shunt, Current,
Voltage, Temp, or None):
11. Type
SHUNT
,
CURRENT
,
VOLTAGE
,
TEMP
, or
NONE
to
specify the type of signal connected to the input
associated to this channel. Then press
ENTER
.
12. If "Shunt" was entered above, the system responds with...
Shunt type: current info
Shunt type (50mv or 100mv):
13. Type
50mv
or
100mv
to specify the shunt size connected
to the input associated to this channel. Then press
ENTER
.
14. If "Current" was entered above, the system responds
with...
4-20 mA signal: current info
4-20 mA signal (Y or N):
15. Type
Y
if this analog channel monitors a remote
measuring module with a 4-20 ma output. Type
N
if this
analog channel monitors any other signal. Then press
ENTER
.
Note:
If
Y
is entered, the analog channel will give a FAIL reading
if the monitored signal drops below 2 mA.
16. If "Voltage" was entered above, the system responds
with...
Full Scale Output: current info
Enter the transducer full-scale output
in Volts:
17. Type the value (in volts) of the maximum voltage to be
measured by this channel.
18. If "Shunt", "Current", "Voltage", or "None" was entered
above as the "Transducer Type", the system responds
with...
Scale Factor: current info
Scale Factor:
19. Type the required scale factor (20000 maximum), then
press
ENTER
.
20. The system responds with...
Monitor type: current info
Monitor type:
21. This parameter applies only to TL1 commands/messages.
Type the name of the unit (10 characters maximum) that
the above alarms are measured in (ex. VOLTDC, CURDC,
etc.), then press
ENTER
. Only alpha characters can be
entered for this parameter. TL1 uses specific values for
this parameter. Refer to TA-NWT-001360 Table 6-1.
22. The system responds with...
Monitor Value Format: current info
Set monitor value format to integer(I)
or decimal(D):
23. This parameter applies only to TL1 commands/messages.
Type I if the monitored value (monval) is a decimal
integer. Type D if the monitored value (monval) is an
unrestricted decimal number. Then press
ENTER
.
24. The system responds with...
Polarity: <present setting>
Polarity (+, -)?:
25. Type ‘+’ (plus symbol) for Positive(default) polarity.
Type ‘-‘ (minus symbol) for Negative polarity
26. The system responds with...
Alarm Limit Mode: N
Alarm Limit Mode (N or B) ?