Installation Manual

NetSureā„¢ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[85 of 149]
Note:
Refer to "Operating LMS1000" in the User Instructions
(Section 5847) for a description of nodes. Section 5847 can be
accessed via the CD (Electronic Documentation Package)
furnished with your system.
1. The system searches for and adds to the database all
Expansion Nodes found on the network. The Nodes are
arbitrarily assigned numbers prefixed with an "X". The "X"
indicates the Node is currently not configured. Also
displayed is the configuration of the Node as it was
programmed at the factory.
Searching for new nodes
Node# Name Spec. Number Ser.#
Loc Echelon Id #
X01 --- 58212190001 12346
L 1A2B3C4D5F6A
X02 --- 58212190001 12346
R 1A2B3C4D5F6B
X03 --- 58212190002 12347
L 1A2B3C4D5F6C
X04 --- 58212190002 12347
R 1A2B3C4D5F6D
2. The system then prompts to select a Node to configure.
Type the number of the Node to configure (as listed).
Press
ENTER
to proceed.
Which node? : X01
3. Enter configuration information as it is displayed. Press
ENTER
to proceed.
Node Number: ---
Node Number: 01
Node Name: ---
Node Name: Main Distribution Bay 1
Spec Number: 58212190001
Spec Number:
Serial Number: 12346
Serial Number:
Location Number: L
Location Number:
Module 1 List Number: --
Module 1 List Number: AB
Module 2 List Number: --
Module 2 List Number: D
Module 3 List Number: --
Module 3 List Number: T
Module 4 List Number: --
Module 4 List Number: BK
4. After all configuration parameters are presented, the
system prompts to save the changes. Type
Y
and press
ENTER
to save the Node's configuration.
Save changes (Y or N): Y
Storing node configuration
5. The system prompts to add channels to the Node's
configuration. Type
Y
then press
ENTER
.
Edit Node Channels (Y or N): Y
6. Add from the available channels those that are active in
the system.
Note:
Type the number(s) of available channels to be
added to the Node's configuration, then press
ENTER. Channels can be specified by entering a
single channel number (e.g. A1, B8), or by entering a
range of channels (e.g. A1-8, B1-12). To continue,
press
ENTER without specifying a channel.
Enter channel (e.g. A12 or A1-6) or D to
display.
Add Channel: A1
Add Channel: A7-11
Add Channel: B1-4
Add Channel:
7. The system prompts to delete channels that were
previously added to the Node's configuration. To
continue, press
ENTER
without specifying a channel.
Enter channel (e.g. A12 or A1-6) or D to
display.
Del Channel:
Del Channel:
8. The system prompts to configure another Node. Type
Y
then press
ENTER
if there are remaining Nodes that need
to be configured. Otherwise type
N
then press
ENTER
.
Repeat the above steps until all Nodes are configured.
Configure another node? (Y or N):
Configuring Analog Channels
Refer to the worksheets (or copies of) located at the end of
"Installing LMS1000" as a guide in programming the various
channels associated with the system.
Note:
This information can also be programmed through the
command CONFIG A_ which is described later in this section.
Note:
Parameters which apply only to TL1 commands/messages do
not appear for configuration if the TL1 software option is not
installed.
Note:
Only "Channel Active", "Channel Name", "Sub-Access Identifier",
"System Alarm Reporting", "Monitor Type", and "Monitor Value
Format" are configurable for MCA Interface channels. The
Operation section in the User Instructions (Section 5847) lists
the MCA Interface channels. Section 5847 can be accessed via
the CD (Electronic Documentation Package) furnished with
your system.
1. The system responds with the first analog channel
default configuration, followed by...
Channel active (Y or N):