Installation Manual

NetSureā„¢ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[84 of 149]
PROCEDURE:
1. After logging onto the system, type
SET SYSTEM
. Then
press
ENTER
.
Command <6>: SET SYSTEM
Setting the Date, Time, Unit Name, Unit Number, System
Identifier, Unit Header, Unit Pager Code, and Pager Delay
Note:
This information can also be programmed through the
commands SET DATE, SET TIME, and SET UNIT which are
described later in this section.
1. The system responds with...
Date is current info.
Use Format mm/dd/yy
2. Type the current date in the format specified, then press
ENTER
.
3. The system responds with...
Time is current info.
Use Format hh:mm:ss
4. Type the current time in the format specified, then press
ENTER
.
5. The system responds with...
LMS1000 v2.0.0
Unit Name: current info - Unit #current
info
System Identifier: current info
Unit Header:
current info
Unit Name:
6. Type the desired unit name (30 characters maximum),
then press
ENTER
.
7. The system responds with...
Unit #
8. Type the desired unit number (4 digits maximum), then
press
ENTER
.
9. The system responds with...
System Identifier:
10. This parameter applies only to TL1 commands/messages.
Type the desired System Identifier (20 characters
maximum), then press
ENTER
. This data parameter is
used to identify the destination of command messages
and the source of response and autonomous messages in
an NMA system.
11. The system responds with...
Unit Header:
12. Type the desired unit header (79 characters maximum),
then press
ENTER
. The unit header is displayed when a
user logs onto the system.
13. The system responds with...
Unit Pager Code:
14. If required, type the desired unit pager code (20
characters maximum),
then press
ENTER
. The Unit Pager
Code is the phone number at which the system is located
followed by any terminating character required. This is
the number that will appear in the display window of the
paging system beeper unit.
15. The system responds with...
Pager Delay:
16. Type the desired pager delay (0-99), then press
ENTER
.
The pager delay is the time delay (in seconds) between
the last digit dialed in a pager phone number and
outputting the pager PIN number.
Configuring Alarm Class Names
If Alarms are to be classified by the Alarm Class feature, enter a
name for each of the available Alarm Classes.
Note:
This information can also be programmed through the
command SET CLASS which is described later in this section.
1. The system responds with the first Programmable Alarm
Classification.
Programmable Alarm Classifications
K1.none
2. Type the name of the Alarm Class (5 characters
maximum), then press
ENTER
.
Note:
To delete a name,
just enter a
SPACE
then press
ENTER
.
Alarm Class Name:
3. The system will display the second through eighth
Programmable Alarm Classification. Enter the required
data for each Programmable Alarm Classification as
described above.
Adding and Configuring LMS1000 Expansion Nodes
This procedure shows the user how to add and configure
Expansion Nodes. Use this procedure if the system contains
586505000/586505500 Expansion Cabinets,
582140000/582140001/582126100 Secondary Bays with
LMS1000 I/O cards, and/or 586505000/586505500 Expansion
Assemblies.
Note:
This information can also be programmed through the
command NODE ADD which is described later in this section.