Installation Manual
NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[81 of 149]
available to users programmed for access to level 4
commands. The commands are divided into the
following levels.
Level 1 Interrogate/Status Commands
Level 2 Display Channel Configuration
Level 3 Set Date & Time
Level 4 Alarm Acknowledge, Alarm Canceling
Level 5 Configure Channels
Level 6 Configure Users, Upload & Download
e. Callback Feature (Y or N): A feature that allows increased
security when accessing the system via its modem. After
a user calls the system and enters his password, the
system will hang-up and call the user back at the
designated phone number.
f. Primary Phone Number (20 Characters maximum): This
phone number is used for callbacks, System Alarm
Reports, and User Reports. The primary phone number is
used only during selectable valid days and hours. Valid
characters include:
0-9 processed as normal DTMF code
* processed as normal DTMF code
# processed as normal DTMF code
B wait for pager system to answer, then transmit
pager ID code
, two second pause (comma)
when used with the TL1 port, only alphanumeric
characters are valid
all other characters are ignored
g. Valid Days & Hours for Primary Phone Number (1-7 with
1=Sunday; 00-23): These variables specify the days and
hours when the primary phone number is used for
callbacks and the primary phone number or primary
Email is used for System Alarm Reports and User Reports.
A range of days is specified by entering the beginning and
ending days of the valid period using numbers to
represent the days. A range of hours is specified by
entering the beginning and ending hour of the valid
period.
h. Alternate Phone Number (20 Characters maximum): This
phone number is used for callbacks, System Alarm
Reports, and User Reports when the current date and
time are not valid. See primary phone number for valid
characters.
i. Primary E-mail: This is the Email address used for System
Alarm Reports and User Reports during the "Valid Days &
Hours for Primary Phone Number".
j. Alternate E-mail: This is the Email address used for
System Alarm Reports and User Reports outside of the
"Valid Days & Hours for Primary Phone Number".
k. Report Device (Modem, Ethernet, X25 [if TL1/X.25 option
installed], or Telnet [if TL1 over Ethernet option
installed]): Allows the user to select a Report Device
(either the system’s modem, Email via the Ethernet port,
or a TL1 network) that the system uses to issue a System
Alarm Report or User Report.
l. Report Mode (Off, Pager, M300, M1200, M2400, M9600,
M28800, M33600, M56000): This prompt appears if
"Modem" is selected above as the Report Device. Allows
the user to select which method of communication is
used when sending System Alarm Reports and User
Reports, either pager or modem at xxx bits/s.
Report Mode (OFF or E-mail): This prompt appears if
"Ethernet" is selected above as the Report Device. E-mail
= System Alarm Reports and User Reports sent via Email.
OFF = alarm reports are not processed.
Report Mode (OFF or TL1): This prompt appears if "X25"
or "Telnet" is selected above as the Report Device. TL1 =
TL1 report messages processed via the TL1 port. OFF =
alarm reports are not processed.
m. Report Retry Time (0-1440 minutes):
Allows the user to
select the number of minutes the system waits before
attempting another callback, User Report, or TL1 report
message in the event the prior attempt failed. Zero
represents no retry. (This retry time has no effect on
System Alarm Reporting.)
n. TL1 Report Condition Interval (0-1440 minutes): This
prompt appears if "X25" or "Telnet" is selected above as
the report device. Specifies how frequently the unit will
attempt a Report Condition message. A value of ‘0’
disables sending of Report Condition messages.
Note:
Parameters o) through u) do not appear if "X25" or
"Telnet" is selected as the Report Device.
o. Occurred Alarm Report (Y or N): Selects sending a "User
Report" of new alarms that have occurred on "user
channels".
p. Retired Alarm Report (Y or N): Selects sending a "User
Report" of alarms that have cleared on "user channels".