Table 12. Terms and Operators for LED Channel and Relay Channel Program Lines
Left Side Terms
Definition
Rn
Relay Channel # n
Ln LED Channel # n
Right Side
Operators
Definition
( )
For grouping expressions
for precedence
!
Logic NOT
&
Logic AND
^
Logic EXCLUSIVE OR
¦
Logic INCLUSIVE OR
Right Side
Terms
Definition
A
Any Analog Alarm
An
Analog Alarm For Input # n
An.l
Alarm Limit l (1-4) for
Analog Input # n)
F Any Function Alarm
Fn Function Alarm For Input # n
Fn.l
Function Alarm Limit l (1-4)
for Function Input # n
B
Any Binary Alarm
Bn
Binary Alarm For Input # n
R
Any Relay Channel Activated
Rn
Relay Channel # n Activated
L
Any LED Channel Activated
Ln
LED Channel # n (Activated
Wn
Day of the Week Specified by # n
(1-7, Sunday=1)
Mn
Month of Year Specified by # n
(1-12)
Dn
Numerical Day of Month
Specified By # n (1-31)
Pn
Programmable Time Period
Specified by # n (See Command
"SET PERIOD")
Cn( )
An Active (true) Term in the Program
if n or More Combinations of Terms
Inside the Parenthesis are Active.
Right Side
Terms
Definition
S1
An Active (true) Term in the Program
if there is any new analog or binary
alarm; true for only one second.
S2
An Active (true) Term in the Program
if the S2 pushbutton on the front of
the LMS1000 is pushed; true for only
one second.
Kn
An Alarm Classification Term, where
n is a number from 1-8 which
represents an alarm class number.
The K term will be active (true) if an
alarm occurs on any analog or
function channel alarm limit, or binary
channel programmed with this alarm
class number in its configuration.
Note:
Relay and LED channels
programmed with an alarm class
number will NOT activate the alarm
class term in a control program.
E1
(Relay
and LED
Channels
Only)
Sequencer Error, Sequencer
Aborted.
Note:
The channel name should reflect
this
entry, such as naming the
channel "Sequencer Aborted".
Note
(When MCA Interface is Used)
1)
DO NOT use VPS/NPS analog channels (A9001-A9114) or
NPS analog channels (A9901-A9907 and Ann51-Ann60) in
relay channel or LED channel program lines.
2)
VPS/NPS binary channels (B9001-B9115) and NPS binary
channels (B9901-B9946 and Bnn01-Bnn60) may be used in
relay channel and LED channel program lines.
Note:
Numerical constants less than one must
have a zero to the left of the decimal point.