PROCEDURE:
1. Type
BOARDS
, then press
ENTER
.
Command <6>: BOARDS
2. The system displays a list of circuit cards installed in the
586505000/586505500 Main Cabinet or LMS1000 cards
installed in the 582140000/582140001/582126100
Primary Power Bay. Check this list to verify that the type
and number of the circuit cards identified match the ones
installed.
3. If circuit cards are not correctly listed, the user should
check to be sure each circuit card is seated properly in the
cabinet or bay mounting connector.
Software Option Verification
This procedure verifies that the required software options are
installed.
PROCEDURE:
1. Type
OPTIONS
, then press
ENTER
.
Command <6>: OPTIONS
2. The system displays a list of all available software options,
and indicates which ones are installed. Check this list to
verify that the required software options are installed.
Note:
Also listed are the LMS1000 communications ports
associated with each installed option, if applicable.
Verifying Programmable Status LED Indicator Operation
This procedure verifies correct operation of the programmable
status LED indicators.
PROCEDURE:
1. Type
SET LED
, then press
ENTER
.
Command <6>: SET LED
2. The system responds with ...
Set LED:
3. Type
1
, then press
ENTER
.
4. Verify that LED indicator 1 located on the main LMS1000
CPU circuit card illuminates.
5. Type
CLR LED
, then press
ENTER
.
Command <6>: CLR LED
6. The system responds with ...
Clear LED:
7. Type
1
, then press
ENTER
.
8. Verify that LED indicator 1 extinguishes.
9. Repeat Steps 1) through 8) entering the numbers, one at
a time,
2
through
8
. Verify that the associated LED
indicator illuminates and extinguishes as described
above.
Verifying Relay Operation
This procedure verifies correct operation of the relay circuit cards
installed in the 586505000/586505500 Main Cabinet or
582140000/582140001/582126100 Primary Power Bay, if
provided.
CAUTION!
DO NOT perform this procedure on any relay
channel that controls an entity that could cause a
service interruption.
Note:
The relay circuit card contains a jumper which may be set to
disable the use of the SET RLY and CLR RLY commands.
Note:
Relay circuit cards installed in 586505000/586505500
Expansion Cabinets or 582140000/582140001/582126100
Secondary Bays cannot be tested until the Expansion Cabinet
or Secondary Bay Node is established in the LMS1000 Network.
This is covered in the System Configuration section.
PROCEDURE:
1. Type
SET RLY
, then press
ENTER
.
Command <6>: SET RLY
2. The system responds with ...
Set Relay:
3. Type
1
, then press
ENTER
.
4. Verify that the external circuit connected to the relay
output associated to this relay channel performs as
expected.
5. Type
CLR RLY
, then press
ENTER
.
Command <6>: CLR RLY
6. The system responds with ...
Clear Relay:
7. Type
1
, then press
ENTER
.
8. Verify that the external circuit connected to the relay
output associated to this relay channel performs as
expected.
9. Repeat Steps 1) through 8) entering the numbers, one at
a time,
2
through
32
, as required. Verify that the external
circuits connected to the relay outputs associated to
these relay channels perform as expected.
Caution