Interconnecting the Expansion Cabinet(s) and Assembly(s) (if
furnished) into the LMS1000 Network (586505000/586505500
Only)
In a 582140000/582140001/582126100 Power System, refer to
the Power System's
Installation Instructions
for LMS Network
interconnections between Bays and optional LMS Expansion
Assembly(s).
Located on the back of the Main and Expansion Cabinets are four
RJ-45 Expansion Ports. Refer to Figure 7 for location. Located on
the Expansion Assembly(s) is one RJ-45 Expansion Port. Refer to
Figure 20 for location. Interconnect these ports as required for
your installation so that each Expansion Cabinet and Expansion
Assembly is connected to the LMS1000 Network (path from each
Expansion Cabinet or Assembly can be traced back to Main
Cabinet). Refer to the next section for cable specifications and
assembly instructions. Refer to Figure 20 for a typical network
interconnect diagram. Refer to SAG586505000/SAG586505500
for maximum cable length specifications. The SAG can be
accessed via the CD (Electronic Documentation Package)
furnished with your system.
LMS1000 Network Cable Specifications
LMS1000 Expansion Cabinets and Expansion Assemblies are
connected to the LMS1000 Main Cabinet network with a multi-
conductor cable that is terminated on both ends with a RJ-45 plug.
These plugs mate with RJ-45 jacks provided throughout the
LMS1000 network.
A cable with RJ-45 plugs attached to both ends may be supplied, or
a length of cable with two unconnected RJ-45 plugs may be
supplied, as ordered. If required, the installer is to assemble the
cable per these specifications and per site requirements.
The recommended cable is a category 5, four twisted pair
conductor, 24 gauge solid copper cable. Emerson Network Power
P/N 156202100. Belden P/N 1585AD15. If this cable is ordered
through Emerson Network Power, specify the required length in 5
feet increments. A six foot cable with appropriate plugs pre-
attached is also available (P/N 421842700).
The required components necessary to terminate the cable are
provided in a kit offered by Emerson Network Power. The Emerson
Network Power part number of this kit is 483589500 and consist
of:
a. Two (2) RJ-45 plugs. Emerson Network Power P/N
247803300. AMP P/N 557315.
LMS1000 Network Cable Assembly
Attach a plug to each end of the cable per Table 10, and the
following instructions:
1. Trim and strip (0.5 – 0.56 inch) jacketed cable using
appropriate, commercially available tools.
Note:
Do not strip insulated wires.
2. Insert the wires completely into the RJ-45 plug. Visually
inspect the assembly to ensure proper routing of the
individual conductors. If using the recommended cable,
follow the color scheme shown in Table 10. Refer to
Figure 9 for the pin numbering scheme of the RJ-45 plug.
3. Terminate the cable using appropriate crimp tool, AMP
P/N 2-231652-1 with die set AMP P/N 853400-1.
Table 10. LMS1000 Network Cable Wire Color Scheme
PIN NO. WIRE COLOR
1
White / Blue Stripe
2 Blue
3 White / Orange Stripe
4
Orange
5 White / Green Stripe
6
Green
7
White / Brown Stripe
8 Brown