leads from unintentional shorts during installation or service.
These resistors should be located as near as possible to the voltage
source to provide maximum protection.
Procedure:
1. 586505000/586505500: To access terminal block TB1
located on a binary circuit card, rotate the two captive
fasteners on the front of the cabinet until the arrow on
the fastener points up or down, and pivot the door open.
or
582140000/582140001/582126100: Open the bay's
front door.
2. Connect the leads as shown in Figure 15. Ensure that the
jumper associated to each input is correctly set, as
previously described in this section. Make connections to
terminals 15 and/or 16 of each binary circuit, as required.
Note:
A single ended connection is required for each binary
input. Battery (+BAT and/or -BAT) is also connected
to the circuit card as determined by the alarm wiring
method used and plant polarity. This is needed only
to complete the binary input path. Completion of
the binary input path creates a contact closure on
the binary channel. +BAT or -BAT is selected for each
input by jumper placement. If all binary inputs
require the same battery potential, only that
potential needs to be connected to the circuit card.
Refer to Figure 16 for typical binary input wiring.
3.
586505000/586505500: If no more connections are to
be made inside the cabinet, close the cabinet door and
secure with the two captive fasteners (arrow on fastener
points towards outside of cabinet).
or
582140000/582140001/582126100: If no more
connections are to be made inside the bay, close the
bay's front door.
Figure 15. Connection to an Eight Input Binary Circuit Card, P/N
506334
B8
B1
Note:
Binary input designations B1 through B8 as shown are for
the circuit card only. The actual binary channel number
depends upon the quantity of binary circuit cards installed
and the location of this binary circuit card in the
system network.
Binary input
wiring connection
terminals
(Refer to Figure 2-5 for proper jumper placement.
This jumper determines the second connection for this input.)
B5
B6
B7
B4
B3
B2
Connections to Battery, as required
+BAT
-BAT
Note:
Needed only to complete binary input
path as determined by placement of
appropriate jumper. If all binary
inputs require the same battery
potential, only that potential needs to
be connected. (see text for additional
clarification)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
TB1
506334