[13 of 149]
Figure 4. Jumper Location, Four Input Analog Circuit Card, P/N 506336
+
A2
A4
A1
A4
A3
A3
A1
A2
+
+
+
+
+
+
+
123
12
3
123
123
J2
J202
J102
J302
123
12
3
123
TB1
Jumper
Input
J2
A4
J102
A3
J202
A2
J302
A1
Place jumper on pins 1 and 2 for 0-60 volt DC inputs.
Connect inputs to terminals designated "Large Signal".
Place jumper on pins 2 and 3 for 20 ma current loop inputs.
Connect inputs to terminals designated "Small Signal".
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Place jumper ONLY
on pin 1 for 50 mv and 100 mv shunt inputs.
Connect inputs to terminals designated "Small Signal".
Large
Signal
Large
Signal
Small
Signal
Small
Signal
Large
Signal
Small
Signal
Large
Signal
Small
Signal
506336