Installation Manual

NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[11 of 149]
Figure 3. Installing the I/O Circuit Cards (cont'd from previous page, cont’d on next page)
* Note:
Two grounding studs are provided. Each
grounding stud contains two nuts. If a
Temperature circuit card is installed, attach
the Green Wire from the circuit card to one
of the grounding studs, below the bottom nut.
Tighten the top nut down to lock the bottom nut.
Temperature
Circuit Card
Grounding Stud
Locations*
LMS Input/Output
(I/O) Circuit Card
4-Input Analog, P/N 506336
8-Input Analog, P/N 514528
12-Input Analog, P/N 520838
8-Input Temperature, P/N 506333
4-Input Binary, P/N 506332
8-Input Binary, P/N 506334
4-Output Relay, P/N 506335
Install LMS I/O Circuit Cards from Left to Right
with Component Side of Circuit Card Facing
the Left as Viewed from the Front.
DO NOT SKIP SLOTS.
582140000
Power System