Installation Manual

NetSureā„¢ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[148 of 149]
Resetting Defaults
This procedure shows the user how to return the parameters listed in Table 15 to their factory default settings using the command SET
DEFAULTS. Refer to "Commands" of the User Instructions (Section 5847) for a typical screen display. Section 5847 can be accessed via the
CD (Electronic Documentation Package) furnished with your system.
Note:
Executing this command will destroy information that has previously been programmed by a user. All channel configurations are also
returned to factory default settings.
Procedure:
1. After logging onto the system, type
SET DEFAULTS.
Then press
ENTER
.
Command <6>: SET DEFAULTS
2. The system responds with...
Execution of this command will DESTROY ALL SYSTEM CONFIGURATIONS and could result in ALARM
CONDITIONS !!
Do you wish to set defaults (Yes or N)?
3. Type
YES
, then press
ENTER
.
4. The system responds with...
Setting system defaults.
Initializing Analog I/O cards.
(only displayed if Analog circuit cards are installed in the system)
Defaults set.
5. Log off of the system. This completes the procedure.
Table 15. Default Settings for System Parameters
Parameter Default Setting
Unit Name
Central Office
Unit Number
1
Unit TCP/IP Address
192.168.1.1
Unit GATEWAY Address
192.168.1.1
GET Community String public
SET Community String private
Trap Addresses (none set)
SNMP Version (for traps sent) V2
Number of Rings before Answering 1
User Timeout Period 300 seconds
Logon Password Number of Access Level Required (1-6)
System Alarm Report Mode Off
User Calling Sequence
(none defined)
Retry Time (System Alarm Report)
10 minutes
Auto-Logoff Time
60 seconds
Sequencer Standby Start Delay 15 seconds
Sequencer Failsafe Timer 60 seconds
AC Restoration Qualification Timer 0 (disabled)
Rectifier Sequencing Routines
Y