Installation Manual

NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[137 of 149]
CONFIG R_
Note:
If "Y" was entered above, the
system responds with...
System Alarm Report mode (Y or
N):
Type
Y
if the system is required to initiate an alarm report via phone
lines if this channel alarms and
N
if not, then press
ENTER
.
Note:
If "Y" was entered above for "Alarm
Type", the system responds with...
Alarm Class Number:
Type the desired alarm class number associated with this channel, then
press
ENTER
. Alarm classes are specified with the numbers 0 through 8,
with 0 representing no alarm class.
Note:
This parameter is configurable only
if the channel is configured as an
Alarm Type.
Condition Type:
This parameter applies only to TL1 commands/messages. Type the
name (20 characters maximum) which describes this alarm or event
state, then press
ENTER
. Only alpha characters can be entered for this
parameter. TL1 uses specific values for this parameter. Refer to
TA-NWT-001360 Tables 5-1 through 5-4.
Note:
This parameter is configurable only
if the channel is configured as an
Alarm Type.
Condition Description:
This parameter applies only to TL1 commands/messages. Type a user-
defined text message (40 characters maximum) which provides a
detailed description of this alarm, event, or condition. Then press
ENTER
. May also be used to describe any action to be taken as a result
of the condition. All printable ASCII characters are valid except for the
percent sign (%), double quotes ("), and the backslash (\).
Note:
This parameter is configurable only
if the channel is configured as an
Alarm Type.
Notification Code:
This parameter applies only to TL1 commands/messages. Type one of
the following codes which describes the severity of this alarm or event
condition, then press
ENTER
.
CR - critical alarm
MJ - major alarm
MN - minor alarm
NA - not alarmed
NR - not reported when event occurs
Note:
This parameter is configurable only
if the channel is configured as an
Alarm Type.
Service Effect Code:
This parameter applies only to TL1 commands/messages. Type one of
the following codes which describes how this alarm or event affects
service, then press
ENTER
.
SA=service-affecting condition, immediate action required
NSA=nonservice-affecting condition, action required
Affected by ACO (Y or N):
Type the characters
Y
or
N
which represent if the alarm can be cut off,
then press
ENTER
. Y=yes, ACO enabled, N=NO, ACO disabled
Cycle Freq (min):
Type the required cycle frequency of the relay channel (0-1440
minutes), then press
ENTER
. When a relay is energized, the system can
be programmed to de-energize the relay at a selected time interval.
This time interval is determined by the relay’s "cycle frequency". This
feature resets external alarm logic that requires an open to close
transition for alarming. During a relay alarm condition, the relay
remains energized for the time duration determined by the value of
the relay’s cycle frequency. Once this time period expires, the system
de-energizes the relay for 15 seconds. The system will then
re-energize the relay if the alarm condition still exists.
If the relay channel is set to be affected by ACO, the cycle frequency is
also used to automatically release the alarm cut-off feature at a
selected time interval determined by the cycle frequency. The system
automatically performs the equivalent of a CLR ACO command at the
end of the "cycle frequency". To disable these features, set the "cycle
frequency" to zero.