Installation Manual

NetSureā„¢ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[134 of 149]
CONFIG L_
Note:
This parameter is configurable only
if the channel is configured as an
Alarm Type.
Condition Type:
This parameter applies only to TL1 commands/messages. Type the
name (20 characters maximum) which describes this alarm or event
state, then press
ENTER
. Only alpha characters can be entered for this
parameter. TL1 uses specific values for this parameter. Refer to
TA-NWT-001360 Tables 5-1 through 5-4.
Note:
This parameter is configurable only
if the channel is configured as an
Alarm Type.
Condition Description:
This parameter applies only to TL1 commands/messages. Type a user-
defined text message (40 characters maximum) which provides a
detailed description of this alarm, event, or condition. Then press
ENTER
. May also be used to describe any action to be taken as a result
of the condition. All printable ASCII characters are valid except for the
percent sign (%), double quotes ("), and the backslash (\).
Note:
This parameter is configurable only
if the channel is configured as an
Alarm Type.
Notification Code:
This parameter applies only to TL1 commands/messages. Type one of
the following codes which describes the severity of this alarm or event
condition, then press
ENTER
.
CR - critical alarm
MJ - major alarm
MN - minor alarm
NA - not alarmed
NR - not reported when event occurs
Note:
This parameter is configurable only
if the channel is configured as an
Alarm Type.
Service Effect Code:
This parameter applies only to TL1 commands/messages. Type one of
the following codes which describes how this alarm or event affects
service, then press
ENTER
.
SA=service-affecting condition, immediate action required
NSA=nonservice-affecting condition, action required
Control Type:
This parameter applies only to TL1 commands/messages. Type the
name of the NMA system external control entity (10 characters
maximum) that this channel is controlling, then press
ENTER
. Only
alpha characters can be entered for this parameter. TL1 uses specific
values for this parameter. Refer to Appendix G of TR-NWT-000833,
issue 5.
Off Delay Time:
Type the required alarm off delay time period* and a modifier*, then
press
ENTER
. The off delay time is the amount of seconds that an alarm
condition must cease before the system recognizes that the alarm
condition ceased.
* Enter a valid value (0-9999) then the modifier (s for seconds, m for
minutes, h for hours). If no modifier entered, modifier defaults to
seconds.
On Delay Time:
Type the required alarm on delay time period* and a modifier*, then
press
ENTER
. The on delay time is the amount of seconds that an alarm
condition must exist before the system recognizes it as an alarm
condition.
* Enter a valid value (0-9999) then the modifier (s for seconds, m for
minutes, h for hours). If no modifier entered, modifier defaults to
seconds.
Save changes (Y or N):
Type
Y
if the above entered data is to be saved in the current LED
configuration file and
N
if not, then press
ENTER
.