Installation Manual

NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[133 of 149]
Changing the LED Channel Configurations
The LED channel configurations can be changed by using the commands CONFIG. The command CONFIG is also described in
"Commands" of the User Instructions (Section 5847). Section 5847 can be accessed via the CD (Electronic Documentation Package)
furnished with your system. The command, when entered, will display a header that contains the current configuration. Then,
individually, the command will list each item that can be changed, showing the current information, and then prompting for new or
revised information to be entered. If the current information does not need to be changed, press
ENTER to continue.
Command CONFIG: If the command CONFIG is entered, the system will ask that you identify which channel you wish to modify. Another
way of entering the command is to identify the desired channel in the command line by typing the channel number after the characters
CONFIG (ex. CONFIG L1). The various information pertaining to an LED Channel that can be changed through this command is described
below. This command is available to users programmed for access to level 6 commands.
Note:
Parameters which apply only to TL1 commands/messages do not appear for configuration if the TL1 software option is not installed.
CONFIG L_
Command <6>: CONFIG L1
Type
CONFIG L1
, then press
ENTER
.
Channel active (Y or N)
Note:
If "Y" is entered, the system will
allow the default configuration
information of the current LED
channel to be changed as shown
below.
Type
Y
if the channel is required to be active and
N
if not, then press
ENTER
.
If "N" was entered above, the system
responds with...
Set channel configuration to
default values? (Y or N):
Type
Y
to change the attributes of this channel to their default values.
Note:
If ”Y” is entered, this command terminates.
If ”N” is entered, the system will allow the default configuration
information of the current LED channel to be changed as shown below.
Name:
Type the desired name for this LED channel (30 characters maximum),
then press
ENTER
.
Color (Red, Green, or Amber):
Type
Red
,
Green
, or
Amber
to specify the color the LED illuminates, then
press
ENTER
.
Sub-access Identifier:
This parameter applies only to TL1 commands/messages. Type the
name (20 characters maximum) of the sub-access identifier that this
channel belongs to, then press
ENTER
. The group of LMS1000 channels
monitoring a sub-entity in an NMA system should have the same
access identifier and sub-access identifier. Only alpha-numeric
characters can be entered for this parameter. TL1 uses specific values
for this parameter. Refer to TA-NWT-001360, Table 4-1.
Alarm Type (Y or N):
Type
Y
if the alarm condition determined by this channel is required to
be recorded in the alarm log (required if System Alarm Reporting is
desired for this channel, and/or an alarm class of 1 through 8 is
assigned to this channel) when it is activated and
N
if not, then press
ENTER
.
Note:
If "Y" was entered above, the
system responds with...
System Alarm Report mode (Y or
N):
Type
Y
if the system is required to initiate an alarm report via phone
lines if this channel alarms and
N
if not, then press
ENTER
.
Note:
If "Y" was entered above for "Alarm
Type", the system responds with...
Alarm Class Number:
Type the desired alarm class number associated with this channel, then
press
ENTER
. Alarm classes are specified with the numbers 0 through 8,
with 0 representing no alarm class.