Installation Manual

NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[132 of 149]
CONFIG F_
Condition Description:
This parameter applies only to TL1 commands/messages. Type a user-
defined text message (40 characters maximum) which provides a
detailed description of this alarm, event, or condition. Then press
ENTER
. May also be used to describe any action to be taken as a result
of the condition. All printable ASCII characters are valid except for the
percent sign (%), double quotes ("), and the backslash (\).
Unit Text:
Type the name of the unit (4 characters maximum) that the above
alarms are measured in (ex. volt, amp, etc.), then press
ENTER
.
Off Delay Time:
Type the required alarm off delay time period* and a modifier*, then
press
ENTER
. The off delay time is the amount of seconds that an alarm
condition must cease before the system recognizes that the alarm
condition ceased.
* Enter a valid value (0-9999) then the modifier (s for seconds, m for
minutes, h for hours). If no modifier entered, modifier defaults to
seconds.
On Delay Time:
Type the required alarm on delay time period* and a modifier*, then
press
ENTER
. The on delay time is the amount of seconds that an alarm
condition must exist before the system recognizes it as an alarm
condition.
* Enter a valid value (0-9999) then the modifier (s for seconds, m for
minutes, h for hours). If no modifier entered, modifier defaults to
seconds.
Save changes (Y or N):
Type
Y
if the above entered data is to be saved in the current function
configuration file and
N
if not, then press
ENTER
.
Note:
If "Y" was entered above, the
system then responds with...
Enter Program Line:
Type the program line (79 characters maximum) which determines the
input value of this channel, then press
ENTER
. Refer to the beginning of
this section for a discussion on program lines.
Note:
When the LMS1000 is used in a 582140000, 582140001,
and 582126100 N
ETSURE Power System that
communicates to the LMS1000 using the LISP port option,
channels F64 and F63 are used to provide the values to
the Power System MCA for ‘Total Rectifier Output’ and
‘External Distribution Load’ status readings respectively.
Any value assigned/calculated in the program lines of
these channels will be passed to the MCA and summed
into the ‘Total Charger Output’ and ‘Total Load Current
respectively (as viewed on LMS1000 channels A9902 and
A9904).