CONFIG F_
Alarm Class Number:
Type the desired alarm class number associated with the third alarm
limit, then press
ENTER
. Alarm classes are specified with the numbers 0
through 8, with 0 representing no alarm class.
Condition Type:
This parameter applies only to TL1 commands/messages. Type the
name (20 characters maximum) which describes this alarm or event
state, then press
ENTER
. Only alpha characters can be entered for this
parameter. TL1 uses specific values for this parameter. Refer to
TA-NWT-001360 Tables 5-1 through 5-4.
Condition Description:
This parameter applies only to TL1 commands/messages. Type a user-
defined text message (40 characters maximum) which provides a
detailed description of this alarm, event, or condition. Then press
ENTER
. May also be used to describe any action to be taken as a result
of the condition. All printable ASCII characters are valid except for the
percent sign (%), double quotes ("), and the backslash (\).
Limit 4 Enabled (Y or N):
Type
Y
to enable this alarm limit or
N
to disable this alarm limit. Then
press
ENTER
.
Limit 4 Value:
Type the required value of the fourth alarm setting (5 characters,
99999 maximum), then press
ENTER
.
Limit 4 Type is High or Low (H
or L):
Type
H
if the fourth alarm setting is a high limit and
L
if the fourth alarm
setting is a low limit, then press
ENTER
.
Limit 4 Name:
Type the desired name of the fourth alarm setting (10 characters
maximum), then press
ENTER
.
Limit 4 Notification Code:
This parameter applies only to TL1 commands/messages. Type one of
the following codes which describes the severity of this alarm or event
condition, then press
ENTER
.
CR - critical alarm
MJ - major alarm
MN - minor alarm
NA - not alarmed
NR - not reported when event occurs
Limit 4 Service Effect Code:
This parameter applies only to TL1 commands/messages. Type one of
the following codes which describes how this alarm or event affects
service, then press
ENTER
.
SA=service-affecting condition, immediate action required
NSA=nonservice-affecting condition, action require
Alarm Class Number:
Type the desired alarm class number associated with the fourth alarm
limit, then press
ENTER
. Alarm classes are specified with the numbers 0
through 8, with 0 representing no alarm class.
Condition Type:
This parameter applies only to TL1 commands/messages. Type the
name (20 characters maximum) which describes this alarm or event
state, then press
ENTER
. Only alpha characters can be entered for this
parameter. TL1 uses specific values for this parameter. Refer to
TA-NWT-001360 Tables 5-1 through 5-4.