CONFIG E_
Note:
If the analog channel selected in
the "Shunt=" step is not associated
to a PCU shunt, the system
responds with...
(name entered above) TR lead =
Type the number of the relay channel connected to the TR or RCC leads
of the rectifier connected to this channel, then press
ENTER
.
Note:
Only use relay channel on circuit cards installed in the
586505000/586505500 Main Cabinet or
582140000/582140001/582126100 Primary Power Bay. DO
NOT use relay circuit cards in Expansion Cabinets for controlling
rectifiers.
Note:
This parameter is not user configurable for PCUs.
Rectifier On when Standby ON
(Y or N):
Type
Y
if it is required to have the rectifier/PCU connected to this
channel to be turned on if a standby source is supplying power to the
rectifier/PCU and
N
if not, then press
ENTER
.
Save changes (Y or N):
Type
Y
if the above entered data is to be saved in the current energy
management configuration file and
N
if not, then press
ENTER
.