CONFIG B_
Condition Type:
This parameter applies only to TL1 commands/messages. Type the
name (20 characters maximum) which describes this alarm or event
state, then press
ENTER
. Only alpha characters can be entered for this
parameter. TL1 uses specific values for this parameter. Refer to
TA-NWT-001360 Tables 5-1 through 5-4.
Condition Description:
This parameter applies only to TL1 commands/messages. Type a user-
defined text message (40 characters maximum) which provides a
detailed description of this alarm, event, or condition. Then press
ENTER
. May also be used to describe any action to be taken as a result
of the condition. All printable ASCII characters are valid except for the
percent sign (%), double quotes ("), and the backslash (\).
Notification Code:
This parameter applies only to TL1 commands/messages. Type one of
the following codes which describes the severity of this alarm or event
condition, then press
ENTER
.
CR - critical alarm
MJ - major alarm
MN - minor alarm
NA - not alarmed
NR - not reported when event occurs
Service Effect Code:
This parameter applies only to TL1 commands/messages. Type one of
the following codes which describes how this alarm or event affects
service, then press
ENTER
.
SA=service-affecting condition, immediate action required
NSA=nonservice-affecting condition, action required
Alarm Condition (CC or CO):
Type the characters
CC
or
CO
which represents the condition required
to activate an alarm, then press
ENTER
.
Alarm Class Number:
Type the desired alarm class number associated with this channel, then
press
ENTER
. Alarm classes are specified with the numbers 0 through 8,
with 0 representing no alarm class.
Off Delay Time:
Type the required alarm off delay time period* and a modifier*, then
press
ENTER
. The off delay time is the amount of seconds that an alarm
condition must cease before the system recognizes that the alarm
condition ceased.
* Enter a valid value (0-9999) then the modifier (s for seconds, m for
minutes, h for hours). If no modifier entered, modifier defaults to
seconds.
Note:
The timing involved in the operation of the rectifier sequencing
feature will be affected if the alarm delay attributes for the binary
channels selected to control the sequencer are configured.
Configuring the "On Delay" or "Off Delay" for the AC Fail / Transfer
input or Standby On / Proper Operate input will postpone
detection (signals may have already been detected by the
transfer device) of an AC Failure or Proper Operate signal by the
rectifier sequencing software.