Installation Manual
NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[118 of 149]
CONFIG A_
Transducer Type (Shunt,
Current, Voltage, Temp, or
None):
Type
SHUNT
,
CURRENT
,
VOLTAGE
,
TEMP
, or
NONE
to specify the type of
signal connected to the input associated to this channel. Then press
ENTER
.
If "Shunt" was entered above, the system
responds with...
Shunt type (50mv or 100mv):
Type
50mv
or
100mv
to specify the shunt size connected to the input
associated to this channel. Then press
ENTER
.
If "Current" was entered above, the system
responds with...
4-20 mA signal (Y or N):
Type
Y
if this analog channel monitors a remote measuring module
with a 4-20 mA output. Type
N
if this analog channel monitors any
other signal. Then press
ENTER
.
Note:
If
Y
is entered, the analog channel will give a FAIL reading if the
monitored signal drops below 2 mA.
If "Voltage" was entered above, the system
responds with...
Enter the transducer full-
scale output in Volts:
Type the value (in volts) of the maximum voltage to be measured by
this channel.
If "Shunt", "Current", "Voltage", or "None" was
entered above as the "Transducer Type", the
system responds with...
Scale Factor:
Type the required scale factor (20,000 maximum), then press
ENTER
.
Monitor type:
This parameter applies only to TL1 commands/messages. Type the
name of the unit (10 characters maximum) that the above alarms are
measured in (ex. VOLTDC, CURDC, etc.), then press
ENTER
. Only alpha
characters can be entered for this parameter. TL1 uses specific values
for this parameter. Refer to TA-NWT-001360 Table 6-1.
Set monitor value format to
integer(I) or decimal(D):
This parameter applies only to TL1 commands/messages. Type I if the
monitored value (monval) is a decimal integer. Type D if the
monitored value (monval) is an unrestricted decimal number. Then
press
ENTER
.
Alarm Polarity (+, -)?:
Type ‘+’ for Positive(default) polarity.
Type ‘-‘ for Negative polarity
Then press
ENTER
.
See Operating LMS1000 in Section 5847 (User Instructions) for further
description and examples.
Alarm Limit Mode (N or B) ?
Type ‘N’ for ‘Normal’ operation.
Type ‘G’ for ‘Global’ command operation.
Then press <ENTER>
Limit 1 Enabled (Y or N):
Type
Y
to enable this alarm limit or
N
to disable this alarm limit. Then
press
ENTER
.
Limit 1 Value:
Type the required value of the first alarm setting (5 characters, 20000
maximum), then press
ENTER
.
Limit 1 Type is High or Low (H
or L):
Type
H
if the first alarm setting is a high limit and
L
if the first alarm
setting is a low limit, then press
ENTER
.
Limit 1 Name:
Type the desired name of the first alarm setting (10 characters
maximum), then press
ENTER
.