Installation Manual

NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[97 of 149]
Save changes (Y or N):
93. Type
Y
if the above entered data is to be saved in the
current function channel configuration and
N
if not, then
press
ENTER
.
94. If ”Y” was entered above, the system responds with...
Enter Program Line:
95. Type the program line (79 characters maximum) which
determines the input value of this channel, then press
ENTER
. Program lines are discussed earlier in this section.
Note:
When the LMS1000 is used in a 582140000,
582140001, and 582126100 N
ETSURE Power
System that communicates to the LMS1000
using the LISP port option, channels F64 and
F63 are used to provide the values to the Power
System MCA for ‘Total Rectifier Output’ and
‘External Distribution Load’ status readings
respectively. Any value assigned/calculated in
the program lines of these channels will be
passed to the MCA and summed into the ‘Total
Charger Output’ and ‘Total Load Current
respectively (as viewed on LMS1000 channels
A9902 and A9904).
96. The system will display the second function channel
configuration. Enter the required data for each function
channel as described above until the system displays the
default configuration of the first LED channel.
Configuring LED Channels
Refer to the worksheets (or copies of) located at the end of
"Installing LMS1000" as a guide in programming the various
channels associated with the system.
Note:
This information can also be programmed through the
command CONFIG L_ which is described later in this section.
Note:
Parameters which apply only to TL1 commands/messages do
not appear for configuration if the TL1 software option is not
installed.
1. After the system responds with the first LED channel
default configuration, the following will be displayed...
Channel active (Y or N):
2. Type
Y
if the channel is required to be active and
N
if not,
then press
ENTER
.
3. If ”N” was entered, the system displays another LED
channel configuration. If ”Y” was entered, the system
allows the default configuration information of the
current LED channel to be changed as shown below.
4. The system responds with...
Name: current info
Name:
5. Type the desired name for this LED channel (30
characters maximum), then press
ENTER
.
6. The system responds with...
Color: current info
Color (Red, Green, or Amber):
7. Type
Red
,
Green
, or
Amber
to specify the color the LED
illuminates, then press
ENTER
.
8. The system responds with...
Sub-access Identifier: current info
Sub-access Identifier:
9. This parameter applies only to TL1 commands/messages.
Type the name (20 characters maximum) of the sub-
access identifier that this channel belongs to, then press
ENTER
. The group of LMS1000 channels monitoring a
sub-entity in an NMA system should have the same
access identifier and sub-access identifier. Only alpha-
numeric characters can be entered for this parameter.
TL1 uses specific values for this parameter. Refer to
TA-NWT-001360, Table 4-1.
10. The system responds with...
Alarm Type: current info
Alarm Type (Y or N):
11. Type
Y
if the alarm condition determined by this channel
is required to be recorded in the alarm log (required if
System Alarm Reporting is desired for this channel,
and/or an alarm class of 1 through 8 is assigned to this
channel) when it is activated and
N
if not, then press
ENTER
.
12. If ”Y” was entered above, the system responds with...
System Alarm Report mode: current info
System Alarm Report mode (Y or N):
13. Type
Y
if the system is required to initiate an alarm report
if this channel alarms and
N
if not, then press
ENTER
.
14. If "Y" was entered above for "Alarm Type", the system
responds with...
Alarm Class Number:
15. Type the desired alarm class number associated with this
channel, then press
ENTER
. Alarm classes are specified
with the numbers 0 through 8, with 0 representing no
alarm class.
16. If ”Y” was entered above for the ALARM TYPE parameter,
the system responds with...
Condition Type: current info
Condition Type: