Installation Manual
NetSure⢠LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[96 of 149]
69. Type
Y
to enable this alarm limit or
N
to disable this alarm
limit. Then press
ENTER
.
70. The system responds with...
Limit 4 Value: current info
Limit 4 Value:
71. Type the required value of the fourth alarm setting (5
digits, 99999 maximum), then press
ENTER
.
72. The system responds with...
Limit 4 Type: current info
Limit 4 Type is High or Low (H or L):
73. Type
H
if the fourth alarm setting is a high limit and
L
if
the fourth alarm setting is a low limit, then press
ENTER
.
74. The system responds with...
Limit 4 Name: current info
Limit 4 Name:
75. Type the desired name of the fourth alarm setting (10
characters maximum), then press
ENTER
.
76. The system responds with...
Limit 4 Notification Code: current info
Limit 4 Notification Code:
77. This parameter applies only to TL1 commands/messages.
Type one of the following codes which describes the
severity of this alarm or event condition, then press
ENTER
.
CR - critical alarm NA - not alarmed
MJ - major alarm NR - not reported when event occurs
MN - minor alarm
78. The system responds with...
Limit 4 Service Effect Code: current
info
Limit 4 Service Effect Code:
79. This parameter applies only to TL1 commands/messages.
Type one of the following codes which describes how this
alarm or event affects service, then press
ENTER
.
SA = service-affecting condition, immediate action
required
NSA = nonservice-affecting condition, action required
80. The system responds with...
Alarm Class Number:
81. Type the desired alarm class number associated with the
fourth alarm limit, then press
ENTER
. Alarm classes are
specified with the numbers 0 through 8, with 0
representing no alarm class.
82. The system responds with...
Condition Type: current info
Condition Type:
83. This parameter applies only to TL1 commands/messages.
Type the name (20 characters maximum) which
describes this alarm or event state, then press
ENTER
.
Only alpha characters can be entered for this parameter.
TL1 uses specific values for this parameter. Refer to
TA-NWT-001360 Tables 5-1 through 5-4.
84. The system responds with...
Condition Description: current info
Condition Description:
85. This parameter applies only to TL1 commands/messages.
Type a user-defined text message (40 characters
maximum) which provides a detailed description of this
alarm, event, or condition. Then press
ENTER
. May also
be used to describe any action to be taken as a result of
the condition. All printable ASCII characters are valid
except for the percent sign (%), double quotes ("), and the
backslash (\).
86. The system responds with...
Unit Text: current info
Unit Text:
87. Type the name of the unit (4 characters maximum) that
the above alarms are measured in (ex. volt, amp, etc.),
then press
ENTER
.
88. The system responds with...
Off Delay Time: current info
Off Delay Time:
89. Type the required alarm off delay time period* and a
modifier*, then press
ENTER
. The off delay time is the
amount of seconds that an alarm condition must cease
before the system recognizes that the alarm condition
ceased.
* Enter a valid value (0-9999) then the modifier (s for
seconds, m for minutes, h for hours). If no modifier
entered, modifier defaults to seconds.
90. The system responds with...
On Delay Time: current info
On Delay Time:
91. Type the required alarm on delay time period* and a
modifier*, then press
ENTER
. The on delay time is the
amount of seconds that an alarm condition must exist
before the system recognizes it as an alarm condition.
* Enter a valid value (0-9999) then the modifier (s for
seconds, m for minutes, h for hours). If no modifier
entered, modifier defaults to seconds.
92. The system responds with...