Installation Manual
NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[93 of 149]
17. The system responds with...
Save changes (Y or N):
18. Type
Y
if the above entered data is to be saved in the
current energy management channel configuration and
N
if not, then press
ENTER
.
19. The system will display the second energy management
channel configuration. Enter the required data for each
energy management channel as described above until
the system displays the default configuration of the first
function channel.
Configuring Function Channels
Refer to the worksheets (or copies of) located at the end of
"Installing LMS1000" as a guide in programming the various
channels associated with the system.
Note:
This information can also be programmed through the
command CONFIG F_ which is described later in this section.
Note:
Parameters which apply only to TL1 commands/messages do
not appear for configuration if the TL1 software option is not
installed.
1. After the system responds with the first function channel
default configuration, the following is displayed...
Channel active (Y or N):
2. Type
Y
if the channel is required to be active and
N
if not,
then press
ENTER
.
3. If ”N” was entered, the system displays another function
channel configuration. If ”Y” was entered, the system
allows the default configuration information of the
current function channel to be changed as shown below.
4. The system responds with...
Name: current info
Name:
5. Type the desired name for this function channel (30
characters maximum), then press
ENTER
.
6. The system responds with...
Sub-access Identifier: current info
Sub-access Identifier:
7. This parameter applies only to TL1 commands/messages.
Type the name (20 characters maximum) of the sub-
access identifier that this channel belongs to, then press
ENTER
. The group of LMS1000 channels monitoring a
sub-entity in an NMA system should have the same
access identifier and sub-access identifier. Only alpha-
numeric characters can be entered for this parameter.
TL1 uses specific values for this parameter. Refer to
TA-NWT-001360, Table 4-1.
8. The system responds with...
System Alarm Report mode: current info
System Alarm Report mode (Y or N):
9. Type
Y
if the system is required to initiate an alarm report
if an alarm limit is exceeded on this channel and
N
if not,
then press
ENTER
.
10. The system responds with...
Monitor type: current info
Monitor type:
11. This parameter applies only to TL1 commands/messages.
Type the name of the unit (10 characters maximum) that
the above alarms are measured in (ex. VOLTDC, CURDC,
etc.), then press
ENTER
. Only alpha characters can be
entered for this parameter. TL1 uses specific values for
this parameter. Refer to TA-NWT-001360 Table 6-1.
12. The system responds with...
Monitor Value Format: current info
Set monitor value format to integer(I)
or decimal(D):
13. This parameter applies only to TL1 commands/messages.
Type I if the monitored value (monval) is a decimal
integer. Type D if the monitored value (monval) is an
unrestricted decimal number. Then press
ENTER
.
14. The system responds with...
Limit 1 Enabled: current info
Limit 1 Enabled (Y or N):
15. Type
Y
to enable this alarm limit or
N
to disable this alarm
limit. Then press
ENTER
.
16. The system responds with...
Limit 1 Value: current info
Limit 1 Value:
17. Type the required value of the first alarm setting (5 digits,
99999 maximum), then press
ENTER
.
18. The system responds with...
Limit 1 Type: current info
Limit 1 Type is High or Low (H or L):
19. Type
H
if the first alarm setting is a high limit and
L
if the
first alarm setting is a low limit, then press
ENTER
.
20. The system responds with...
Limit 1 Name: current info
Limit 1 Name:
21. Type the desired name of the first alarm setting (10
characters maximum), then press
ENTER
.