NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Specification Number: 586505000 and 586505500 Model Number: LMS1000 Firmware Version 12.0 Also for the LMS Monitoring System factory integrated into Spec. Nos. 582140000, 582140001, and 582126100 NetSure™ Power Systems (NPS).
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) This page is intentionally blank. Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Table of Contents Admonishments Used in this Document ............................................................................................................... iv Static Warning ...................................................................................................................................................... v FCC Information ..........................................................
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Energy Management Connections (when used w/ 'traditional' rectifiers external to the system) ....................... 47 Sequential Start Connections ............................................................................................................................ 48 LMS Dual MCA Interface Software Option ...............................................................................................
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Setting Local Port Communications Parameters ............................................................................................... 83 Setting Gateway Port Parameters (if Gateway Software Option Installed) ......................................................... 83 Setting System Configuration ..........................................................................................................
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Admonishments Used in this Document DANGER! Warns of a hazard the reader will be exposed to that will likely result in death or serious injury if not avoided. (ANSI, OSHA) Danger Warning Caution WARNING! Warns of a potential hazard the reader may be exposed to that could result in death or serious injury if not avoided.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Static Warning This equipment contains static sensitive components. The warnings listed below must be observed to prevent damage to these components. Disregarding any of these warnings may result in personal injury or damage to the equipment. 1. Strictly adhere to the procedures provided in this document. 2.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) FCC Information The MCA Interface Modem Option (if installed) has been granted a registration number by the Federal Communications Commission, under Part 68 rules and regulations for direct connection to the telephone lines. In order to comply with these FCC rules, the following instructions must be carefully read and applicable portions followed completely: a.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) General Information and Installation Checklist Optional Expansion Assembly(s) Mounted in Customer Equipment Optional Modem Circuit Card Installed CPU Circuit Card(s) Installed Four Input Analog Circuit Card Installed after Making any Jumper Adjustment as Required Eight Input Analog Circuit Card Installed Twelve Input Analog Circuit Card Installed Four Input Binary Circuit Card Ins
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Connections Made to all Eight Input Binary Circuit Cards Installed Connections Made to all Four Output (Form-C) Relay Circuit Cards Installed Connections Made to all Eight Input Temperature Circuit Cards Installed Optional Expansion Assembly(s) (if furnished) Interconnected to Customer Equipment All 586505000/586505500 Expansion Cabinets, 582140000/582140001/582126100 Secondary Bays, and/o
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) and grounded through the CPU circuit card via a metal standoff located on the modem circuit card and a supplied screw. Circuit Card Handling Warning WARNING! Before handling any circuit card, read and follow the instructions contained on the Static Warning Page located at the beginning of this document. Before performing the next steps, study the diagram in Figure 1.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 1. Installing the Modem Circuit Card (cont'd on next page) 586505000 Main Cabinet (586505500 similar) Main CPU Circuit Card Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 1. Installing the Modem Circuit Card (cont'd from previous page, cont'd on next page) 582140000 Power System Primary Bay 582126100 Power System Primary Bay MONITORING AND CONTROL SECTION Optional LMS Monitoring System Main CPU Circuit Card Location Spec. No. 582140000 shown, Spec. No. 582126100 similar. MONITORING AND CONTROL SECTION Front door assembly removed in illustration for clarity.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 1. Installing the Modem Circuit Card (cont'd from previous page) Screw Sheetmetal Bracket 582140000/582140001/ 582126100 Only 582140000/582140001/ 582126100 Only Modem Circuit Card P/N 508951 (Trace Side Up) Plastic Standoffs (3) CPU Circuit Card P/N 514024 or 521185 J10 on CPU Circuit Card. J1 on Modem Circuit Card.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CPU circuit card P/N 506153 is to be installed in the 586505000/586505500 LMS1000 Expansion Cabinet(s) or 582140000/582140001/582126100 Secondary Bay(s).
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 2.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) and sets the input to either monitor 50 mv and 100 mv DC shunt inputs, 0-60 volt DC inputs, or 20 ma current loop inputs. Refer to Figure 4, and set each jumper for the type of input to be monitored.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) grounding studs provided inside the bay. Refer to Figure 3 for location. Place the lug of the green wire below the bottom nut. Tighten the top nut down to lock the bottom nut. 10. Supplied with your system documentation is an I/O circuit card label sheet (P/N 520538). These labels allow circuit card identification without removing a circuit card.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 3.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 3.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 4. Jumper Location, Four Input Analog Circuit Card, P/N 506336 16 15 3 2 1 14 J2 13 12 3 2 1 Jumper Input J2 A4 J102 A3 J202 A2 J302 A1 11 J102 10 3 2 1 J202 TB1 9 8 7 6 3 2 1 J302 5 4 3 2 506336 1 Place jumper ONLY on pin 1 for 50 mv and 100 mv shunt inputs. Connect inputs to terminals designated "Small Signal". 3 2 1 Place jumper on pins 1 and 2 for 0-60 volt DC inputs.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 5. Jumper Location, Eight Input Binary Circuit Card, P/N 506334 3 2 1 Input J8 B8 J7 B7 J6 B6 J5 J4 B4 J3 B3 J2 B2 J1 B1 14 J7 13 3 2 1 12 J6 11 3 2 1 J5 B5 3 2 1 10 TB1 J4 3 2 1 J3 3 2 1 J2 3 2 1 J1 506334 Place jumper on pins 1 and 2 to complete a -BAT connection for this input Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 6. Jumper Location, Four Output (Form-C) Relay Circuit Card, P/N 506335 16 15 14 13 12 To disable the commands SET RLY and CLR RLY, place the jumper provided on the two pins of J1. 11 10 TB1 J1 9 8 To enable the commands SET RLY and CLR RLY, remove the jumper from the two pins of J1. The jumper may be stored on ONE of the pins. 7 6 5 4 3 2 506335 Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Making Electrical Connections Wiring Considerations All electrical connections are made without DC input power applied to the system. All wiring and branch circuit protection should follow the current edition of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NPFA) National Electrical Code (NEC), and applicable local codes.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 7. 586505000/586505500 Terminal Location and Identification (cont’d on next page) 586505000 (586505500 similar) J4 (located behind bracket) CPU Circuit Card in Main Cabinet J4 1 2 3 4 5 6 External Hardware Fail Alarm Spec. No: 58650500, 586505500 Model No: LMS1000 [17 of 149] Note: Relay Contacts are Energized During Normal Operation and Deenergized During an Alarm Condition.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 7. 586505000/586505500 Terminal Location and Identification (cont'd from previous page, cont’d on next page) 586505000 (586505500 similar) Front View (Main Cabinet) RS-232 (Located on CPU Circuit Card, Accessible through Front Door) 9-Pin Female D-Type Connector 5 1 9 6 For Local Terminal Connection List 85: AC Analyzer Port or List 86: TL1/X.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 7. 586505000/586505500 Terminal Location and Identification (cont'd from previous page) 586505000 (586505500 similar) Front View (Expansion Cabinet) Shelf Grounding Stud (10-32) RJ-45 System Network Ports (Expansion Ports) DC Input 586505000 (586505500 similar) Rear View (Expansion Cabinet) Access Opening and Cable Channel for Connections to I/O Circuit Cards Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 8. 582140000/582140001/582126100 LMS Terminal Location and Identification (cont'd on next page) 582140001 Power System 582126100 Power System 582140000 Power System MONITORING AND CONTROL SECTION MONITORING AND CONTROL SECTION Spec. No. 582140000 shown, Spec. No. 582126100 similar.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 8.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 8. 582140000/582140001/582126100 LMS Terminal Location and Identification (cont'd from previous page, cont'd on next page) Detail B 582140000 and 582126100 Power Systems LMS Ethernet Port (Primary Bay Only) (RJ-45) Spec. No. 582140000 shown, Spec. No. 582126100 similar.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 8.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 8. 582140000/582140001/582126100 LMS Terminal Location and Identification (cont'd from previous page, cont'd on next page) Detail C 582140001 Power System 582140000 and 582126100 Power Systems Spec. No. 582140000 shown, Spec. No. 582126100 similar.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 8. 582140000/582140001/582126100 LMS Terminal Location and Identification (cont'd from previous page) Detail D 582140001 Power System 582140000 and 582126100 Power Systems Spec. No. 582140000 shown, Spec. No. 582126100 similar.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 582140000/582140001/582126100 Power System: If no more connections are to be made inside the bay, close the front door. External CPU/Hardware Fail Alarm Connections The external CPU/hardware fail alarm connections are made to terminal block J4 located on the CPU circuit card installed in the 586505000/586505500 LMS1000 Main Cabinet or 582140000/582140001/582126100 Primary Power Bay.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Gateway Port Connections (if Gateway Software Option is installed) Internal Modem Port Connections The Gateway Software Option allows the LMS1000 to emulate a “dumb” RS-232 asynchronous terminal interface. When installed, user input through either a local or remote LMS1000 port is directed to the customer equipment connected to the LMS1000 Gateway port.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) OEM1 Port Connections (if required) (586505000/586505500 Only) Connections to the OEM1 port are made to a 9-pin female D-type jack located on the rear of the Main Cabinet, labeled "OEM1 (RS-232)". Refer to Figure 7 for jack location. Refer to Table 3 for jack configuration. The port's function is determined by the LMS1000 Software Options or LMS1000 Specialty Interfaces installed.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Table 4.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 3. Terminate the cable using appropriate crimp tool, AMP P/N 2-231652-1 with die set AMP P/N 853400-1. Figure 9. RJ-45 Plug Attaching 9-Pin Male D-Type Plug 1. Trim and strip (0.75 inch) jacketed cable using appropriate, commercially available tools. 2. Attach the crimp type contacts to the wires of the cable using a crimp tool, AMP P/N 90302-1, or 90312-1, or 404494-7.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Door Access Controller (DAC) Port (if 586505000/586505500 List 80 installed) Connect the OEM3 Port to a Desarrollos Digitales Door Access Controller Model MKC-1. OEM3 port pin assignments are as shown in Table 7. Note: Recommended to use a Desarrollos Digitales Isolation Board (Model DTP-1-485 / 96-DC24-T, E) between the DAC and LMS1000.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 11. Connection to a Four Input Analog Circuit Card, P/N 506336 when monitoring voltages, or a 49.9Ω fusible resistor when monitoring shunts. The protection devices should be located as near as possible to the voltage or current source to provide maximum protection. 16 15 Recommended Maximum Analog Input Loop Lengths: Shunt Inputs: maximum 2,000 ft. loop length. Voltage Inputs: maximum 1,000 ft.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Procedure: 1. 586505000/586505500: To access terminal block TB1 located on an analog circuit card, rotate the two captive fasteners on the front of the cabinet until the arrow on the fastener points up or down, and pivot the door open. or 582140000/582140001/582126100: Open the bay's front door. 2. Connect the leads as shown in Figure 12. 3.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) points towards outside of cabinet). or 582140000/582140001/582126100: If no more connections are to be made inside the bay, close the bay's front door. Figure 13.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 3. leads from unintentional shorts during installation or service. These resistors should be located as near as possible to the voltage source to provide maximum protection. Procedure: 1. 2.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 16.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 16. Typical Binary Input Wiring (cont'd from previous page, cont'd on next page) Typical Binary Input Wiring -48V Plant Binary Circuit Card 506334 1 2 3 4 -BAT +BAT TB1 5 6 7 8 9 10 11 12 13 14 15 16 (+BAT) ABS BAT (-48V) Alarm Contact ABS BAT (-48V) Alarm Contact Alarm Contact Alarm Contact Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 16.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 16. Typical Binary Input Wiring (cont'd from previous page) Typical Binary Input Wiring +24V Plant Binary Circuit Card 506334 1 2 3 4 -BAT +BAT TB1 5 6 7 8 9 10 11 12 13 14 15 16 ABS BAT (+24V) (-BAT) Alarm Contact ABS BAT (+24V) Alarm Contact Alarm Contact Alarm Contact Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 17. Connection to a Four Output (Form-C) Relay Circuit Card, P/N 506335 FOUR OUTPUT (FORM-C) RELAY CIRCUIT CARD P/N 506335 CONNECTIONS Connections to a relay circuit card are made to terminal block TB1 located at the edge of the circuit card. Refer to "Making Connections to an LMS1000 Input/Output (I/O) Circuit Card" in this section for terminal block TB1 connection information.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 18. Connection to an Eight Input Temperature Circuit Card, P/N 506333 EIGHT INPUT TEMPERATURE CIRCUIT CARD P/N 506333 CONNECTIONS Connections to a temperature circuit card are made to terminal block TB1 located at the edge of the circuit card. Refer to "Making Connections to an LMS1000 Input/Output (I/O) Circuit Card" in this section for terminal block TB1 connection information.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Table 8.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Table 9.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 19. Optional Expansion Assembly Connector Locations I/O Ports J19 34 18 1 50 33 17 17 33 50 1 18 34 RJ-45 System Network Port (Expansion Port) I/O Ports J18 Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Interconnecting the Expansion Cabinet(s) and Assembly(s) (if furnished) into the LMS1000 Network (586505000/586505500 Only) In a 582140000/582140001/582126100 Power System, refer to the Power System's Installation Instructions for LMS Network interconnections between Bays and optional LMS Expansion Assembly(s). Located on the back of the Main and Expansion Cabinets are four RJ-45 Expansion Ports.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Figure 20. Typical LMS1000 Network Interconnects + - Main Cabinet + - Expansion Cabinet Expansion Assembly Expansion Assembly + - Expansion Cabinet + - Expansion Cabinet Expansion Assembly Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Note: When the LMS1000 is used in a 582140000, Energy Management Connections (when used w/ 'traditional' rectifiers external to the system) 582140001, and 582126100 NETSURE Power System that communicates to the LMS1000 using the LISP port option, Energy Management RFA’s are summed together and total number of rectifiers failures is passed to the MCA and used in determining ‘Rectifier Minor’ and ‘Rectifier
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) for energy management (as described in the previous procedure), these binary inputs are also used for sequential start and no additional binary input connections are required. Sequential Start Connections Note: The LMS1000 Energy Management and Sequencing features are not for use in Spec. Nos. 582140000, 582140001, or 582126100 Power Systems. • Note: Requires the Sequential Start software option.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) LMS Dual MCA Interface Software Option Logging Onto the System Refer to the LMS documentation (especially Section 5847) for description, configuration, and operation of the LMS Dual MCA Interface feature. Refer to Spec. Nos. 582140000, 582140001, or 582126100 Power System documentation for system interconnections information.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) PROCEDURE: 1. Type BOARDS, then press ENTER. Command <6>: 2. 3. 8. Verify that LED indicator 1 extinguishes. 9. Repeat Steps 1) through 8) entering the numbers, one at a time, 2 through 8. Verify that the associated LED indicator illuminates and extinguishes as described above.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Logging Off of the System Installation Logs/Worksheets This procedure shows the user how to terminate the current communication session. Refer to the following tables. PROCEDURE: 1. Type BYE, then press ENTER. Command <6>: BYE 2. The screen displays a user logged off response. Configuring the System The system requires configuration information to be entered, refer to "Configuring LMS1000". Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) y Spec.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Configuring LMS1000 Getting Started This section requires you to have an understanding of the general operation of the system. Specifically, you must: • know how to access the system using a local or remote terminal. • have an understanding of the conventions used in accessing the system. • have an understanding of the conventions used in an SNMP interface.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) TRAPS ADD Command: Adds a new SNMP Trap recipient to the list of TRAP hosts. Unit Pager Code: The number which appears in the display window of the paging system beeper unit. Pager Delay (0-99 seconds): Determines the time delay in seconds between the last digit dialed in a pager phone number and outputting the pager PIN number. TRAPS VERSION Command: Change the version of SNMP TRAPS sent by the system.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Netmask Address Program Lines In the format of nnn.nnn.nnn.nnn, where 0 ≤ nnn ≤ 255. Note: Only one user at a time has access to the system internal Description: A netmask is a series of bits designed to 'mask' certain portions of an IP address. The standard netmask for a class C network like FlashNet is 255.255.255.0 - basically the last octet, .
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Table 11. Terms and Operators for Function Channel Program Lines Left Side Terms Right Side Terms Right Side Operators Left Term Definition Fn Function Channel # n Right Term Definition An Value of input connected to analog channel # n Fn Value of input determined by function channel # n nn.nn Any constant (e.g. 52.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Table 12. Terms and Operators for LED Channel and Relay Channel Program Lines Left Side Terms Rn Ln Right Side Terms A An An.l F Fn Fn.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Examples of Various Types of Program Lines Refer to Table 13 for example program lines and explanations. Table 13. Example Control Program Lines Program Line R0001=A Explanation Relay 1 will energize when an alarm is turned in for any analog channel. R0002=B0005 Relay 2 will energize when an alarm is turned in for binary channel #5.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) alarm limit is exceeded. An alarm condition for a relay or LED channel is defined as when a preprogrammed condition occurs which causes the relay to energize and the LED to illuminate. Program Line Time Periods Program lines for relay and LED channels can contain a programmable time period term. This term is Pn, where n is a number from 1 through 8 which specifies one of the eight available time periods.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) current reading, and it has a high alarm limit of –6.0 amps to detect a high float current. It can then also have a high limit of +100.0 amps to detect a high discharge current. So, in this example there are two high alarms, with opposite polarity. 4-20 mA signal (Y or N): Allows simple programming of analog channels when monitoring 4-20 ma current loop input signals.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) or channel to which it applies. May also be used to describe any action to be taken as a result of the condition. All printable ASCII characters are valid except for the percent sign (%), double quotes ("), and the backslash (\). g. h. i. Unit Text (4 Characters maximum): Describes the analog input’s unit of measure.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Condition Description (40 characters maximum): This parameter applies only to TL1 commands/messages. A user-defined text message which provides a detailed description of the alarm, event, or condition of the limit or channel to which it applies. May also be used to describe any action to be taken as a result of the condition.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) d. Alarm Class Number (0-8): Assigns one of the 8 alarm classifications to this channel. (0 represents no alarm class.) e. Condition Type (20 characters maximum): This parameter applies only to TL1 commands/messages. A description of this alarm or event state. Only alpha characters can be entered for this parameter. TL1 uses specific values for this parameter.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) h. i. j. k. Affected by ACO (Y or N): An Alarm Cut-Off feature allows temporary disabling of existing alarms. This feature is for applications where programmable relays are used as alarm relays. For alarm cut-off to be functional, the appropriate relay channel has to be configured for alarm cut-off.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) time are not valid. See primary phone number for valid characters. available to users programmed for access to level 4 commands. The commands are divided into the following levels. e. f.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) q. r. System Alarm Reporting Persistent Alarm Report (Y or N): Selects periodically sending a "User Report" of alarms that still exist on "user channels". Persistent Alarm Report Period (0-1440 minutes): This prompt appears if "Y" is selected above for the Persistent Alarm Report parameter. Specifies how frequently the unit will attempt a Persistent Alarm Report.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Initial Configuration PROCEDURE: 1. Note: If configuration information has been saved from another LMS1000 by using the DOWNLOAD command, this information can be copied into this system by using the UPLOAD command. Refer to "Operating LMS1000" in the "User Instructions" (Section 5847) for additional information.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 12. Type the desired unit header (79 characters maximum), then press ENTER. The unit header is displayed when a user logs onto the system. PROCEDURE: 1. After logging onto the system, type SET SYSTEM. Then press ENTER. 13. The system responds with...
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Note: Refer to "Operating LMS1000" in the User Instructions 6. (Section 5847) for a description of nodes. Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system. 1. 2. Note: Type the number(s) of available channels to be added to the Node's configuration, then press ENTER. Channels can be specified by entering a single channel number (e.g.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 2. Type Y if the channel is required to be active and N if not, then press ENTER. 3. If ”N” was entered, the system displays another analog channel configuration. If ”Y” was entered, the system allows the default configuration information of the current analog channel to be changed as shown below. 4.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 41. Type the desired alarm class number associated with the first alarm limit, then press ENTER. Alarm classes are specified with the numbers 0 through 8, with 0 representing no alarm class. 27. 27) Type ‘N’ for ‘Normal’ operation. Type ‘G’ for ‘Global’ command operation Then press 28. The system responds with... 42. The system responds with...
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Limit 3 Enabled: current info Limit 3 Enabled (Y or N): Limit 2 Notification Code: current info Limit 2 Notification Code: 55. This parameter applies only to TL1 commands/messages. Type one of the following codes which describes the severity of this alarm or event condition, then press ENTER. CR - critical alarm NA - not alarmed MJ - major alarm NR - not reported when event occurs MN - minor alarm 56.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 78. The system responds with... severity of this alarm or event condition, then press ENTER. Condition Type: current info Condition Type: 79. This parameter applies only to TL1 commands/messages. Type the name (20 characters maximum) which describes this alarm or event state, then press ENTER. Only alpha characters can be entered for this parameter. TL1 uses specific values for this parameter.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 101. Type the name of the unit (4 characters maximum) that the above alarms are measured in (ex. volt, amp, etc.), then press ENTER. Note: The "Alarm Condition" attribute of the MCA Interface channels is not configurable. The Operation section in the User Instructions (Section 5847) lists the MCA Interface channels.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 12. The system responds with... Condition Description: current info Condition Description: 13. This parameter applies only to TL1 commands/messages. Type a user-defined text message (40 characters maximum) which provides a detailed description of this alarm, event, or condition. Then press ENTER. May also be used to describe any action to be taken as a result of the condition.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) default configuration of the first energy management channel. 10. Type the rated full load input capacity (in amperes) of the rectifier connected to this channel (5 digits maximum), then press ENTER. Configuring Energy Management Channels (if Energy Management Software Option furnished) Note: This parameter is not user configurable for PCUs, this value is automatically obtained by the software.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) TL1 uses specific values for this parameter. Refer to TA-NWT-001360, Table 4-1. 17. The system responds with... Save changes (Y or N): 18. Type Y if the above entered data is to be saved in the current energy management channel configuration and N if not, then press ENTER. 8. 19. The system will display the second energy management channel configuration.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 32. The system responds with... 22. The system responds with... Limit 2 Enabled: current info Limit 2 Enabled (Y or N): Limit 1 Notification Code: current info Limit 1 Notification Code: 23. This parameter applies only to TL1 commands/messages. Type one of the following codes which describes the severity of this alarm or event condition, then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 59. This parameter applies only to TL1 commands/messages. Type one of the following codes which describes the severity of this alarm or event condition, then press ENTER. specified with the numbers 0 through 8, with 0 representing no alarm class. 46. The system responds with... Condition Type: current info Condition Type: 47. This parameter applies only to TL1 commands/messages.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Condition Type: current info Condition Type: 69. Type Y to enable this alarm limit or N to disable this alarm limit. Then press ENTER. 71. Type the required value of the fourth alarm setting (5 digits, 99999 maximum), then press ENTER. 83. This parameter applies only to TL1 commands/messages. Type the name (20 characters maximum) which describes this alarm or event state, then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Name: current info Name: Save changes (Y or N): 93. Type Y if the above entered data is to be saved in the current function channel configuration and N if not, then press ENTER. 5. Type the desired name for this LED channel (30 characters maximum), then press ENTER. 94. If ”Y” was entered above, the system responds with... 6. The system responds with... Enter Program Line: 95.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 17. This parameter applies only to TL1 commands/messages. Type the name (20 characters maximum) which describes this alarm or event state, then press ENTER. Only alpha characters can be entered for this parameter. TL1 uses specific values for this parameter. Refer to TA-NWT-001360 Tables 5-1 through 5-4. 18. The system responds with... Condition Description: current info Condition Description: 19.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) channel as described above until the system displays the default configuration of the first relay channel. 10. If ”Y” was entered above, the system responds with...
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 20. If ”Y” was entered above for the ALARM TYPE parameter, the system responds with... Service Effect Code: current info Service Effect Code: 21. This parameter applies only to TL1 commands/messages. Type one of the following codes which describes how this alarm or event affects service, then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Enter New #: 2. levels once a person is logged on to the system. Additionally, a user cannot change his own password unless he is programmed for access level 6. Type the desired number of rings that the system waits before answering an incoming telephone call (99 rings maximum), then press the ENTER key. The new value is displayed.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Note: If System Alarm Reports and User Reports are to be 15. The primary phone number or primary Email will be used by the system only during valid days and hours, as programmed below. 16. The system responds with... initiated through a pager, do not enter an alternate phone number. 26. The system responds with... From Day: current info From Day: Primary E-mail: current info Primary E-mail: 17.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Type Off or E-mail. OFF = alarm reports are not processed. E-mail = System Alarm Reports and User Reports sent via Email. Then press ENTER. If "X25" or "Telnet" was typed above as the Report Device, the system responds with... Report Mode: current info Report Mode (Off or TL1): Type Off or TL1. OFF = alarm reports are not processed. TL1 = TL1 report messages processed via the TL1 port. Then press ENTER. 33.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Type the number(s) of the channels to be deleted from the user configuration, then press ENTER. Channels can be specified by entering a single channel number (e.g. A0001, B0008), or by entering a range of channels (e.g. A0001-0008, L0001-0012). To exit, press ENTER without specifying a channel.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 7. in the sequence in the event of an unsuccessful attempt to report an alarm condition. return, or line feed being entered before terminating a communication session. The system responds with... Note: The TL1 port has a session timeout feature which operates independently from the user timeout feature. Auto-Logoff Time (seconds): 8. Type the required auto-logoff time (30 to 600 seconds).
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Gateway Address SNMP Version Use the command IP GATEWAY and configure the Gateway address. Refer to "Commands" in the User Instructions (Section 5847) for further information on the use of this command. Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system. Use the command TRAPS VERSION and configure the SNMP version for traps sent.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Enter Base Rectifier Cycle Period (1-365 days): stops energy management and turns on all rectifiers/PCUs. Note: The alarm limits for A9001 are the settings of the VPS/NPS Power System's battery on discharge alarm, 50% battery on discharge alarm, high voltage alarm 1, and high voltage alarm 2. 5.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) equipment to start. Also, the Sequencer Failsafe Timer and AC Restoration Qualification Timer features can be configured. Each rectifier/PCU controlled by the sequencer must be configured into an Energy Management Channel, even if the energy management software option is not installed.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Note: If "N" is entered, all rectifiers/PCUs will be turned on simultaneously after the transfer back to AC power. 4. The system responds with... AC Fail/Transfer Input= current info AC Fail/Transfer Input= 5. 6. Type the number of the binary channel connected to the AC fail/transfer signal, then press ENTER. If the binary channel displayed is the correct number, press the ENTER key to proceed.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) The timer starts when a signal is received indicating that the commercial AC is restored. The standby sequencer (if configured) operates normally until the timer expires. When the timer expires, all rectifiers/PCUs are turned off and the AC sequencer starts. If AC fails before the timer expires, the timer is deactivated. For the TL1 over Ethernet software option, the system responds with...
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) 13. The system responds with... Save changes (Y or N): 14. Type Y if the above entered data is to be saved in the TL1 port parameter configuration and N if not. Then press ENTER. 15. The system responds with...
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Enter channel (e.g. A0012 or A0001-0006) or D to display. Add channel: 9. Type D to display a complete list of channels previously linked to the current access identifier. The channel number, previously configured channel name, and previously configured channel sub-access identifier are displayed. Type the number(s) of all additional channels to be linked to this access identifier, then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) • You set the monitored battery thermal runaway condition and battery thermal runaway voltage using the command BATTERY THERMAL. Refer to the Commands section in the LMS1000 User Instructions (Section 5847). Other Examples Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Checking for Alarms Subsequent Configuration This procedure shows the user how to check to see if any alarms are activated in the system before placing the system into service. After initial programming, various features of the system initially programmed using the SET SYSTEM command can be reprogrammed separately, as explained in the section. PROCEDURE: 1.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) SET UNIT Command <6>: SET UNIT Type SET UNIT, then press ENTER. Unit Name: Type the desired unit name (30 characters maximum), then press ENTER. Unit # Type the desired unit number (4 digits maximum), then press ENTER. System Identifier: This parameter applies only to TL1 commands/messages. Type the desired System Identifier (20 characters maximum), then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Add Channel: B1-4 Add Channel: Module 4 List Number: BK 5. After all configuration parameters are presented, the system prompts to save the changes. Type Y and press ENTER to save the Node's configuration. 8. Save changes (Y or N): Y Storing node configuration 6. Enter channel (e.g. A12 or A1-6) or D to display. Del Channel: Del Channel: The system prompts to add channels to the Node's configuration.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Changing the Analog Channel Configurations The analog channel configurations can be changed by using the command CONFIG. The command CONFIG is also described in "Commands" of the User Instructions (Section 5847). Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system. The command, when entered, will display a header that contains the current configuration.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG A_ Transducer Type (Shunt, Current, Voltage, Temp, or None): Type SHUNT, CURRENT, VOLTAGE, TEMP, or NONE to specify the type of signal connected to the input associated to this channel. Then press ENTER. If "Shunt" was entered above, the system responds with... Shunt type (50mv or 100mv): Type 50mv or 100mv to specify the shunt size connected to the input associated to this channel.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG A_ Limit 1 Notification Code: This parameter applies only to TL1 commands/messages. Type one of the following codes which describes the severity of this alarm or event condition, then press ENTER. CR - critical alarm MJ - major alarm MN - minor alarm NA - not alarmed NR - not reported when event occurs Limit 1 Service Effect Code: This parameter applies only to TL1 commands/messages.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG A_ Alarm Class Number: Type the desired alarm class number associated with the second alarm limit, then press ENTER. Alarm classes are specified with the numbers 0 through 8, with 0 representing no alarm class. Condition Type: This parameter applies only to TL1 commands/messages. Type the name (20 characters maximum) which describes this alarm or event state, then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG A_ Condition Description: This parameter applies only to TL1 commands/messages. Type a userdefined text message (40 characters maximum) which provides a detailed description of this alarm, event, or condition. Then press ENTER. May also be used to describe any action to be taken as a result of the condition.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG A_ Off Delay Time: Type the required alarm off delay time period* and a modifier*, then press ENTER. The off delay time is the amount of seconds that an alarm condition must cease before the system recognizes that the alarm condition ceased. * On Delay Time: Type the required alarm on delay time period* and a modifier*, then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Changing the Binary Channel Configurations The binary channel configurations can be changed by using the commands CONFIG. The command CONFIG is also described in "Commands" of the User Instructions (Section 5847). Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system. The command, when entered, will display a header that contains the current configuration.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG B_ Condition Type: This parameter applies only to TL1 commands/messages. Type the name (20 characters maximum) which describes this alarm or event state, then press ENTER. Only alpha characters can be entered for this parameter. TL1 uses specific values for this parameter. Refer to TA-NWT-001360 Tables 5-1 through 5-4. Condition Description: This parameter applies only to TL1 commands/messages.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG B_ On Delay Time: Type the required alarm on delay time period* and a modifier*, then press ENTER. The on delay time is the amount of seconds that an alarm condition must exist before the system recognizes it as an alarm condition. * Enter a valid value (0-9999) then the modifier (s for seconds, m for minutes, h for hours). If no modifier entered, modifier defaults to seconds.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Changing the Energy Management Channel Configurations The energy management channel configurations can be changed by using the command CONFIG. The command CONFIG is also described in "Commands" of the User Instructions (Section 5847). Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG E_ Note: If the analog channel selected in the "Shunt=" step is not associated to a PCU shunt, the system responds with... (name entered above) TR lead = Type the number of the relay channel connected to the TR or RCC leads of the rectifier connected to this channel, then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Changing the Function Channel Configurations The function channel configurations can be changed by using the command CONFIG. The command CONFIG is also described in "Commands" of the User Instructions (Section 5847). Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system. The command, when entered, will display a header that contains the current configuration.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG F_ Set monitor value format to integer(I) or decimal(D): This parameter applies only to TL1 commands/messages. Type I if the monitored value (monval) is a decimal integer. Type D if the monitored value (monval) is an unrestricted decimal number. Then press ENTER. Limit 1 Enabled (Y or N): Type Y to enable this alarm limit or N to disable this alarm limit. Then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG F_ Limit 2 Notification Code: This parameter applies only to TL1 commands/messages. Type one of the following codes which describes the severity of this alarm or event condition, then press ENTER. CR - critical alarm MJ - major alarm MN - minor alarm NA - not alarmed NR - not reported when event occurs Limit 2 Service Effect Code: This parameter applies only to TL1 commands/messages.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG F_ Alarm Class Number: Type the desired alarm class number associated with the third alarm limit, then press ENTER. Alarm classes are specified with the numbers 0 through 8, with 0 representing no alarm class. Condition Type: This parameter applies only to TL1 commands/messages. Type the name (20 characters maximum) which describes this alarm or event state, then press ENTER.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG F_ Condition Description: This parameter applies only to TL1 commands/messages. Type a userdefined text message (40 characters maximum) which provides a detailed description of this alarm, event, or condition. Then press ENTER. May also be used to describe any action to be taken as a result of the condition.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Changing the LED Channel Configurations The LED channel configurations can be changed by using the commands CONFIG. The command CONFIG is also described in "Commands" of the User Instructions (Section 5847). Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system. The command, when entered, will display a header that contains the current configuration.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG L_ Note: This parameter is configurable only if the channel is configured as an Alarm Type. Condition Type: This parameter applies only to TL1 commands/messages. Type the name (20 characters maximum) which describes this alarm or event state, then press ENTER. Only alpha characters can be entered for this parameter. TL1 uses specific values for this parameter.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG L_ Note: If "Y" was entered above, the system responds with... Enter Program Line: Spec. No: 58650500, 586505500 Model No: LMS1000 Type the program line (79 characters maximum) which determines when the LED illuminates, then press ENTER. Refer to the beginning of this section for a discussion on program lines.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Changing the Relay Channel Configurations The relay configurations can be changed by using the commands CONFIG. The command CONFIG is also described in "Commands" of the User Instructions (Section 5847). Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system. The command, when entered, will display a header that contains the current configuration.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG R_ Note: If "Y" was entered above, the system responds with... System Alarm Report mode (Y or N): Type Y if the system is required to initiate an alarm report via phone lines if this channel alarms and N if not, then press ENTER. Note: If "Y" was entered above for "Alarm Type", the system responds with...
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) CONFIG R_ Control Type: This parameter applies only to TL1 commands/messages. Type the name of the NMA system external control entity (10 characters maximum) that this channel is controlling, then press ENTER. Only alpha characters can be entered for this parameter. TL1 uses specific values for this parameter. Refer to Appendix G of TR-NWT-000833, issue 5.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Changing the Number of Rings before Answer Use the command SET ANSWER. Refer to "Commands" in the User Instructions (Section 5847) for further information on the use of this command. Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system. Changing the User Configurations The user configurations can be changed by using the command SET USERS.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) SET USERS Primary Phone: Type the primary phone number of the user that the system will use for callbacks, System Alarm Reports, and User Reports (20 characters maximum), then press ENTER. Note: If the alarm report is to be initiated through a pager, set the user phone number to that of the paging system.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) SET USERS Report Device (Modem, Ethernet, X25 [only if TL1/X.25 option installed], or Telnet [only if TL1 over Telnet option installed]): Type the desired report device (select Modem, Ethernet, X25, or Telnet) that the system uses to issue System Alarm Reports and User Reports, then press ENTER. Note: "Modem" = LMS1000 Modem "Ethernet" = Email notification via Ethernet Port "X25" = TL1/X.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) SET USERS Note: If "Y" was entered above, the system responds with... Persistent Alarm Report Period: Type the number of minutes (as referenced from midnight each day) that the system will wait before contacting the user with another persistent "User Report" (0-1440 minutes), then press ENTER. As an example, if a time period of 90 minutes is specified, the system reports at Midnight, 1:30 am, 3:00 am, etc.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) SET USERS Enter channel (e.g. A0012 or A0001-0006) or D to display. Del Channel: Spec. No: 58650500, 586505500 Model No: LMS1000 Type D to display a complete list of channels in the user configuration. Type the number(s) of the channels to be deleted from the user configuration, then press ENTER. Channels can be specified by entering a single channel number (e.g.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Adding or Deleting Channels from the User Configurations The user configurations can be changed in the regards of adding or deleting channels by using the command SET USERS. The command SET USER was described earlier in this section. Channels can also be added to or deleted from the currently logged on user’s configuration through the command SET CHANNELS which is described below.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Setting Alarm Class Names If Alarms are to be classified by the Alarm Class feature, enter a name for each of the available Alarm Classes. Procedure: 1. After logging onto the system, type SET CLASS. Then press ENTER. Command <6>: SET CLASS Programmable Alarm Classifications K1.none K2.none K3.none K4.none 2. K5.none K6.none K7.none K8.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Changing System Alarm Reporting or Individual User Reports Parameters of individual User Reports and/or System Alarm Reporting were determined using the command SET SYSTEM. System Alarm Reporting parameters can be changed as described below. Refer to the command SET USERS in this section if it is desired to change individual User Reporting parameters.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Configuring Channels Into Groups If the command CONFIG is entered, the system will ask that you identify which group you wish to modify. Another way of entering the command is to identify the desired group in the command line by typing the group number after the characters CONFIG (ex. CONFIG G1).
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) Resetting Defaults This procedure shows the user how to return the parameters listed in Table 15 to their factory default settings using the command SET DEFAULTS. Refer to "Commands" of the User Instructions (Section 5847) for a typical screen display. Section 5847 can be accessed via the CD (Electronic Documentation Package) furnished with your system.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) NetPerform™ Optimization Services At Emerson Network Power, we understand the importance of reliable equipment – it’s critical to both your business and your bottom line. That is why we offer a wide array of services to meet all of your network infrastructure needs. Customer Service (Pre-Shipment) Email CustomerService.ESNA@Emerson.com Phone 1.800.800.
NetSure™ LMS Data Processing Unit Installation Instructions, Section 5879 (Issue BA, April 7, 2014) The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Emerson Network Power, Energy Systems, North America, Inc.