Application Guide

System Application Guide SAG586505000
Spec. No. 586505000 (Model LMS1000) SAG586505500
Spec. No. 586505500 (Model LMS1000) Issue AZ, April 7, 2014
Page 27 of 62
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
designation and input/output number is identical to that of the input or output
associated to it.
Installed optional LMS1000 I/O circuit cards in the 586505000/586505500 Main
Cabinet or 582140000/582140001/582126100 Primary Bay and each
586505000/586505500 Expansion Cabinet or 582140000/582140001/582126100
Secondary Bay are automatically detected by LMS1000 firmware. Inputs and outputs
are automatically assigned consecutive numbers (per cabinet or bay) for each type
detected, starting with the circuit card of that type installed in the left most position (as
viewed from the front). Types are A for analog, B for Binary, and R for relay.
Temperature inputs are mapped to analog channels.
The Node Number is a fixed number for the 586505000/586505500 Main Cabinet
(Node 00), and includes all I/O's associated to the 586505000/586505500 Main
Cabinet. For the 582140000/582140001/582126100, Node 00 is the grouping of
LMS1000 I/O cards installed in the Primary Bay. Node 00 also includes the LED,
Function, and Energy Management channels. For both 586505000/586505500 and
582140000/582140001/582126100, you assign Node Numbers (21-89) to the
groupings of LMS1000 I/O cards installed in 586505000/586505500 Expansion
Cabinets and 582140000/582140001/582126100 Secondary Bays during the Initial
Start-Up procedure.
Input numbers for the LMS1000 MCA Interface are pre-assigned (The LMS1000 MCA
Interface provides additional analog channels and binary channels. These channels
are dedicated to the LMS1000 MCA Interface, and are automatically mapped to
monitor predetermined MCA parameters.). The Node Number for the LMS1000 MCA
Interface is 90 for all Vortex or N
ETSURE Power Systems except the Spec. Nos. listed
next. The Node Number for the LMS1000 MCA Interface to Spec. Nos. 582140000,
582140001, and 582126100 N
ETSURE Power Systems is 99.
Input numbers for the LMS1000 Interface to Spec. Nos. 582140000, 582140001, and
582126100 N
ETSURE Power System Bays are pre-assigned (The LMS1000 Bay
Interface provides additional analog channels and binary channels. These channels
are dedicated to the LMS1000 Bay Interface, and are automatically mapped to monitor
predetermined parameters.). The Node Number for each Bay is 1 through 20, starting
with the Primary Bay.
The LMS1000 also provides self diagnostic alarms on binary channels B0081 through
B0099.
Example: A0001,
A represents an analog input/channel
00 represents the 586505000/586505500 Main Cabinet Node or
582140000/582140001/582126100 Primary Bay LMS1000 I/O Grouping Node
(cannot be changed)
01 represents input/channel #01
Example: A3001,
A represents an analog input/channel
30 represents the 586505000/586505500 Expansion Cabinet Node or
582140000/582140001/582126100 Secondary Bay LMS1000 I/O Grouping
Node set as Node #30 (set when network initially established)
01 represents input/channel #01
Example: A4001,
A represents an analog input/channel
40 represents the 586505000/586505500 Expansion Assembly Node set as
Node #40 (set when network initially established)
01 represents input/channel #01