Application Guide
System Application Guide SAG586505000
Spec. No. 586505000 (Model LMS1000) SAG586505500
Spec. No. 586505500 (Model LMS1000) Issue AZ, April 7, 2014
Page 25 of 62
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SPECIFICATIONS
1. 586505000/586505500 LMS1000 SYSTEM
1.1 Environmental Ratings
1.1.1 Operating Ambient Temperature Range: -40°C to +60°C (-40°F to +140°F).
1.1.2 Storage Temperature Range: -40°C to +85°C (-40°F to +185°F).
1.1.3 Humidity: This system is capable of operating in an ambient relative humidity range of 0% to
95%, noncondensing.
1.1.4 Altitude: The maximum operating ambient temperature should be derated by 10°C at an
elevation of 10,000 feet above sea level. For elevations between 3,000 feet and 10,000 feet,
derate the maximum operating ambient temperature linearly.
1.1.5 Safety Compliance:
(A) This unit is UL Recognized to the requirements of UL 1950, Standard for Information
Technology Equipment, for use in Telephone, Electronic Data Processing or Information
Processing Equipment.
(B) This unit meets the requirements of CSA 22.2, No. 950 and is tested and Certified by UL
("c UR") for use in Telephone, Electronic Data Processing or Information Processing
Equipment.
1.2 Firmware Specifications
Note: If connected to an MCA, the MCA Interface provides additional analog and binary channels.
These channels are dedicated to monitor predetermined MCA parameters.
1.2.1 The unit supports multiple Users logged in at a time, except as noted in (B) below.
(A) The unit supports fixed IP addresses and does not support the DHCP protocol.
(B) The unit supports a single TELNET session.
1.2.2 Users: 8, maximum.
1.2.3 Analog Channels: 700, maximum, and MCA interface channels.
1.2.4 Binary Channels: 700, maximum, and MCA interface channels.
1.2.5 Function Channels: 64, maximum.
1.2.6 Relay Channels: 100, maximum.
1.2.7 LED Channels: 8, maximum.
1.2.8 Energy Management Channels: 80, maximum.
1.2.9 Groups of Channels: 8, maximum.
1.2.10 Information Pages: 3, maximum.
1.2.11 Status Pages: 16, maximum.
1.2.12 Programmable Commands: 8, maximum.
1.3 Node Specifications
1.3.1 Maximum Number of Nodes Supported: 25.
1.3.2 Maximum Length of Node Cabling:
(A) Node-to-Node: 250 Meters.
(B) Total Wire Length of All Node-to-Node Segments: 450 Meters (1476 Feet).
This is the maximum length of the entire LMS100 Network, and is calculated by adding up
the length of every network cable used to interconnect the Main Cabinet, Expansion
Cabinets, and Expansion Assemblies. Refer to the Installation Instructions (Section 5879)
for cable assembly instructions.