Application Guide

System Application Guide SAG586505000
Spec. No. 586505000 (Model LMS1000) SAG586505500
Spec. No. 586505500 (Model LMS1000) Issue AZ, April 7, 2014
Page 13 of 62
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Restrictions
Not for use in Expansion Assemblies.
Maximum number of binary points that can be monitored is dependent on how many open I/O slots are
available in the system network and maximum number of binary channels the system supports. Each
586505000/586505500 cabinet holds up to ten (10) I/O circuit cards. Refer to "Firmware Specifications"
under "Specifications" in this document for number of binary channels supported.
Note: When LMS1000 is connected to an MCA, the MCA Interface does not require connections to analog,
binary, or relay circuit cards. The MCA Interface provides binary inputs independently from the binary
circuit cards installed.
Ordering Notes
1) Order one (1) List 31 binary circuit card for every eight (8) binary points to be monitored using LMS1000.
2) For recommended protection on input wiring, order current limit resistor kits as required per List BA, BB,
and BC.
List 40: Four (4) Output Form-C Relay Circuit Card
Features
Provides four relays each with one set of Form-C relay contacts.
These relays are used for control or alarm applications and can be programmed by the user.
Relays may also be manually forced "on" (energized) (SET RLY). Any relay forced on can also be
manually turned off (CLR RLY). (A jumper is provided on the relay circuit card to enable/disable the SET
RLY and CLR RLY commands.)
The relay circuit cards can also be programmed to work with the energy management and/or sequential
start option, if ordered (relays are not required to provide energy management and/or sequential start to a
VPS/NPS Power System).
Refer to the "Specifications" section of this document for further information.
Restrictions
Not for use in Expansion Assemblies.
Maximum number of relay outputs that can be provided is dependent on how many open I/O slots are
available in the system network and maximum number of rely channels the system supports. Each
586505000/586505500 cabinet holds up to ten (10) I/O circuit cards. Refer to "Firmware Specifications"
under "Specifications" in this document for number of relay channels supported.
Note: When LMS1000 is connected to an MCA, the MCA Interface does not require connections to analog,
binary, or relay circuit cards. When energy management and/or sequencing option is ordered, relays
are not required to control the VPS/NPS PCUs.
Note: Also available in a Spec. No. 582140000, 582140001, and 582126100 Power System are MCA
Customer Alarm Relay circuit cards. Refer to SAG582140000, SAG582140001, and SAG582126100.
Ordering Notes
1) Order one (1) List 40 relay circuit card for every four (4) relay contacts to be provided by LMS1000.
List 60: LMS1000 Display Option (for use in later version 586505000 19" cabinets)
Features
Provides a front panel display and keypad.
Allows local access to the system without a terminal.
You can view plant voltage and load current, view active alarms, perform channel scans, view the Events
Log and Alarm Log, view channel statistics, and view battery discharge history.
Restrictions
Home