Application Guide
SAG586505000 System Application Guide
SAG586505500 Spec. No. 586505000 (Model LMS1000)
Issue AZ, April 7, 2014 Spec. No. 586505500 (Model LMS1000)
Page 12 of 62
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Restrictions
Not for use in Expansion Cabinets and Expansion Assemblies.
This circuit card must only be used for adjacent cells in a common battery string. The input requires the inter-
cell connector to be the negative (–) input on one cell and the positive (+) input for the next one. This cannot
be used for pilot cells in multiple battery strings.
A maximum of six (6) cards may be installed in the Main Cabinet
Maximum number of analog points that can be monitored is dependent on how many open I/O slots are
available in the system network and maximum number of analog channels the system supports. Each
586505000/586505500 cabinet holds up to ten (10) I/O circuit cards. Refer to "Firmware Specifications"
under "Specifications" in this document for number of analog channels supported.
Analog inputs should be protected by a fuse in each lead.
Ordering Notes
1) Order one (1) List 23 analog circuit card for every twelve (12) battery cells to be monitored using
LMS1000.
2) Order in-line fuse kits as required per List BE, BF, or P/N 535135.
List 30: Four (4) Input Binary Circuit Card
Features
♦ Monitors 0-60 volts AC/DC double ended binary inputs.
♦ Each circuit card provides four (4) binary inputs to the system. Each input requires two connections
(source and return).
♦ Refer to the "Specifications" section of this document for further information.
Restrictions
Not for use in Expansion Assemblies.
Maximum number of binary points that can be monitored is dependent on how many open I/O slots are
available in the system network and maximum number of binary channels the system supports. Each
586505000/586505500 cabinet holds up to ten (10) I/O circuit cards. Refer to "Firmware Specifications"
under "Specifications" in this document for number of binary channels supported.
Note: When LMS1000 is connected to an MCA, the MCA Interface does not require connections to analog,
binary, or relay circuit cards. The MCA Interface provides binary inputs independently from the binary
circuit cards installed.
Ordering Notes
1) Order one (1) List 30 binary circuit card for every four (4) binary points to be monitored using LMS1000.
2) For recommended protection on input wiring, order current limit resistor kits as required per List BA, BB,
and BC.
List 31: Eight (8) Input Binary Circuit Card
Features
♦ Monitors 0-60 volts AC/DC single ended inputs.
♦ Each circuit card provides eight (8) binary inputs to the system. Each input requires only one connection
(source), plus a single +BAT and/or -BAT connection for all inputs as required.
♦ The other connection point for each binary input is made via the placement of the appropriate jumper on
the circuit card. This jumper either applies +BAT or -BAT to this connection point. This simplifies wiring
to the binary inputs since +BAT and/or -BAT, as required, only has to be connected to the circuit card at
one point.
♦ Refer to the "Specifications" section of this document for further information.