List 21: Eight (8) Input Temperature Circuit Card
Features
♦ Monitors temperature probe inputs.
♦ Each circuit card provides eight (8) temperature inputs to the system (mapped as analog channels).
♦ Refer to the "Specifications" section of this document for further information.
Restrictions
Not for use in Expansion Assemblies.
Maximum number of temperature points that can be monitored is dependent on how many open I/O slots are
available in the system network and maximum number of analog channels the system supports. Each
586505000/586505500 cabinet holds up to ten (10) I/O circuit cards. Refer to "Firmware Specifications"
under "Specifications" in this document for number of analog channels supported.
Ordering Notes
1) Order one (1) List 21 temperature circuit card for every eight (8) temperature probes to be monitored
using LMS1000.
2) Order temperature probes as required per List ST and SU.
List 22: Eight (8) Input Analog Circuit Card
Features
♦ Monitors 50 mv shunt inputs.
♦ Each circuit card provides eight (8) analog inputs to the system.
♦ Refer to the "Specifications" section of this document for further information.
Restrictions
Not for use in Expansion Assemblies.
This circuit card can only be used for 50mV shunts on the same discharge bus. None of the 8 inputs on any
given card may exceed –0.15 to +0.95 V between inputs. The card to card voltage differential does not
matter. These cards may not be used for RIM applications. For RIM applications, use the universal analog
circuit card 586505000 and 586505500 List 20.
Maximum number of analog points that can be monitored is dependent on how many open I/O slots are
available in the system network and maximum number of analog channels the system supports. Each
586505000/586505500 cabinet holds up to ten (10) I/O circuit cards. Refer to "Firmware Specifications"
under "Specifications" in this document for number of analog channels supported.
Shunt inputs should be protected by a 49.9 ohm resistor.
Note: When LMS1000 is connected to an MCA, the MCA Interface does not require connections to analog,
binary, or relay circuit cards. The MCA Interface provides analog inputs independently from the
analog circuit cards installed.
Ordering Notes
1) Order one (1) List 22 analog circuit card for every eight (8) analog points to be monitored using LMS1000.
2) Order current limit resistor kits as required per List BA, BB, and BC.
List 23: Twelve (12) Input Analog Circuit Card
for Measuring Individual Battery Cell Voltages
Features
♦ Monitors individual battery cell voltages.
♦ Each circuit card provides twelve (12) analog inputs to the system.
♦ Refer to the "Specifications" section of this document for further information.