List 10: Common Equipment for
One (1) LMS1000 Expansion Assembly
Features
♦ Provides one (1) LMS1000 EXPANSION ASSEMBLY.
♦ Refer to the "Specifications" section of this document for further
information.
Restrictions
The Expansion Assembly analog inputs can only be used for 50mV
shunts on the same discharge bus. None of the 24 inputs on any
given Expansion Assembly may exceed –0.15 to +0.95 V between
inputs. Each of the 8 binary channels are only activated by a -48V
signal (typical of a fuse alarm bus).
Ordering Notes
1) Order as required to monitor fixed points outside an Emerson Network Power Power System.
2) Order LMS1000 network cables as required per the "ACCESSORY" section.
3) Also order the following as required to terminate customer wiring to the J18/J19 D-type connectors
provided on the assembly.
a) D-Sub Connector Housing (Male): Emerson Network Power P/N 116694 (Tyco P/N 1658641-2).
b) Crimp-Type Pins (Male): Emerson Network Power P/N 245381800 (Tyco P/N 66506-3 [supplied on a
strip] or P/N 66506-9 [supplied loose]).
c) Cable Clamp Housing: Emerson Network Power P/N 116731 (Tyco P/N 748677-5).
d) Jack Screw Male Kit: Emerson Network Power P/N 116737 (Tyco P/N 747784-8).
e) Hand Crimping Tool: Pro Crimper II Tyco P/N 58448-2.
List 20: Four (4) Input Analog Circuit Card
Features
♦ Monitors voltages, shunts, and current loops.
♦ Each circuit card provides four (4) analog inputs to the system.
♦ Refer to the "Specifications" section of this document for further information.
Restrictions
Not for use in Expansion Assemblies.
Maximum number of analog points that can be monitored is dependent on how many open I/O slots are
available in the system network and maximum number of analog channels the system supports. Each
586505000/586505500 cabinet holds up to ten (10) I/O circuit cards. Refer to "Firmware Specifications"
under "Specifications" in this document for number of analog channels supported.
Shunts should be protected by a 49.9 ohm resistor. All other analog inputs should be protected by a fuse in
each lead.
Note: When LMS1000 is connected to an MCA, the MCA Interface does not require connections to analog,
binary, or relay circuit cards. The MCA Interface provides analog inputs independently from the
analog circuit cards installed.
Ordering Notes
1) Order one (1) List 20 analog circuit card for every four (4) analog points to be monitored using LMS1000.
2) Order current limit resistor kits as required per List BA, BB, and BC.
3) Order in-line fuse kits as required per List BE, BF, or P/N 535135.
4) Also available is a 130VDC Monitoring Wire Harness. See ACCESSORY INFORMATION section for
description. Order one (1) P/N 520839 130VDC Monitoring Wire Harness per 130VDC input to be
monitored, as required.