User manual
Connections and Configuration
19 Liebert
®
Liqui-tect
®
3.4 RS422 Liebert SiteScan
®
Web Connector
The Liebert Liqui-tect panel will interface with Liebert’s SiteScan Web
enterprise monitoring system. Liebert SiteScan can be used to monitor the
Liebert Liqui-tect panel from a host computer and silence the audible alarm.
The terminal block connector, TB8, is on the bottom edge of the board, near
the left corner.
To connect the Liebert SiteScan Web to the Liebert Liqui-tect panel:
1. Disconnect electrical power to the Liebert Liqui-tect panel.
2. If necessary, remove a conduit knockout to permit wire entry into the
Liebert Liqui-tect panel enclosure.
3. Bring the wire(s) into the Liebert Liqui-tect panel enclosure through a
conduit knockout or access slot.
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block. Note
that the wires are polarity sensitive.
5. Tighten the screw until it holds the wire snugly.
3.5 Disable the Audible Horn
The panel’s audible horn is enabled by default. You may disable it as follows:
1. Set DIP switch 1, the first switch, to the ON position (up) to disable the audible horn.
2. Press the reset button to initiate the change.
To re-enable the horn, set DIP switch 1, the first switch, to the OFF position (down) and press the
reset button.