3.2 Connecting Alarm Outputs
The Zone 1 and Zone 2 alarm outputs, found in the top right corner
of the Liebert Liqui-tect panel, provide a contact output for a leak
and a cable break for each zone. As an example, the outputs may
provide alarms to an auxiliary alarm panel or building
management system. To determine the proper wire size, see Table
4 - Wiring specifications.
A wiring key beside each terminal block indicates whether the
connected output is wired for Normally Open (NO) or Normally
Closed (NC).
An alarm relay wired as an unsupervised point (energized for
alarm) must be wired to the Normally Open (NO) and Common (C)
contacts.
An alarm relay wired as a supervised point (de-energized for alarm)
must be wired to the Normally Closed (NC) and Common (C)
contacts.
To connect an output:
1. Disconnect electrical power to the Liebert Liqui-tect panel.
2. If necessary, remove a conduit knockout to permit wire entry into the Liebert Liqui-tect panel
enclosure.
3. Bring the wire(s) into the Liebert Liqui-tect panel enclosure through a conduit knockout or access
slot.
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.
5. Tighten the screw until it holds the wire snugly.
3.3 Connecting to a Building Maintenance System or External Alarm System
Two analog output connector blocks permit the user to connect
auxiliary notification equipment to monitor the distance of the leak
and cable fault alarms. The terminal blocks are on the right side of
the Liebert Liqui-tect panel printed circuit board, just above the
leak detection cable connectors. To determine the proper wire size,
see Table 4 - Wiring specifications.
To connect an input:
1. Disconnect electrical power to the Liebert Liqui-tect panel.
2. If necessary, remove a conduit knockout to permit wire entry
into the Liebert Liqui-tect panel enclosure.
3. Bring the wire(s) into the Liebert Liqui-tect panel enclosure through a conduit knockout or access
slot.
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.
5. Tighten the screw until it holds the wire snugly.