Specifications
Liebert XDC and Liebert XDP
72
5.2 Liebert XDP Standard Features
• Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel
plates, copper brazed.
• Pumps—Centrifugal type, end suction, internally cooled, canned rotor design.
• Cabinet and Frame—Custom powder painted steel panels. A hinged control access panel opens
to a second front panel, which is a protected enclosure for all high-voltage components. Frame is
constructed of 14 gauge heliarc welded tubular steel and painted using an auto-deposition coating
system.
• Liebert iCOM—The Liebert iCOM offers the highest capabilities in unit control, communication
and monitoring of Liebert Precision Cooling units. The Liebert iCOM is a factory-installed assem-
bly. Operating conditions and status are indicated on the unit display, which is mounted either on
the unit or on the wall, depending on application details (see user manual, SL-16644). The control
system also monitors unit operation and activates an alarm when any of the specified factory pre-
set conditions are exceeded.
The unit includes two temperature-humidity sensors to aid in effective cooling.
Figure 70 Liebert XDP dimensions
Table 31 Liebert XDP dimensions
Model
Dimensional Data inches (mm) Shipping Weight, lb (kg)
A B * C D E Domestic Export
Liebert
XDP160
38 (965) 34 (864) 33-1/8 (841) 33 (838) 36 (914) 990 (449) 1067 (484)
* The dimension does not include the bezel of the disconnect switch.
Unit Dimensional Data
Floor Cutout Dimensions
E
D
A
Overall
C
Side Panel
B
Overall
DPN001598
D
Unit Base
E
Unit Base
78"
(1981mm)
11"
(279mm)
5
"
(1
2
7
m
m
)
1" (25mm)
2-3/8"
(60mm)
The shaded area indicates
a recommended clearance
of 36" (914mm) for component
access.