Specifications

Liebert XDC and Liebert XDP
72
5.2 Liebert XDP Standard Features
Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel
plates, copper brazed.
Pumps—Centrifugal type, end suction, internally cooled, canned rotor design.
Cabinet and Frame—Custom powder painted steel panels. A hinged control access panel opens
to a second front panel, which is a protected enclosure for all high-voltage components. Frame is
constructed of 14 gauge heliarc welded tubular steel and painted using an auto-deposition coating
system.
Liebert iCOM—The Liebert iCOM offers the highest capabilities in unit control, communication
and monitoring of Liebert Precision Cooling units. The Liebert iCOM is a factory-installed assem-
bly. Operating conditions and status are indicated on the unit display, which is mounted either on
the unit or on the wall, depending on application details (see user manual, SL-16644). The control
system also monitors unit operation and activates an alarm when any of the specified factory pre-
set conditions are exceeded.
The unit includes two temperature-humidity sensors to aid in effective cooling.
Figure 70 Liebert XDP dimensions
Table 31 Liebert XDP dimensions
Model
Dimensional Data inches (mm) Shipping Weight, lb (kg)
A B * C D E Domestic Export
Liebert
XDP160
38 (965) 34 (864) 33-1/8 (841) 33 (838) 36 (914) 990 (449) 1067 (484)
* The dimension does not include the bezel of the disconnect switch.
Unit Dimensional Data
Floor Cutout Dimensions
E
D
A
Overall
C
Side Panel
B
Overall
DPN001598
D
Unit Base
E
Unit Base
78"
(1981mm)
11"
(279mm)
5
"
(1
2
7
m
m
)
1" (25mm)
2-3/8"
(60mm)
The shaded area indicates
a recommended clearance
of 36" (914mm) for component
access.