Technical Specifications

Liebert XDC and Liebert XDP
80
5.1.1 Liebert XDC Optional Features
Water / Glycol Condensers—A water/glycol floor stand condenser option is available for heat
rejection requirements. The water/glycol floor stand can be installed beneath the Liebert XDC or
nearby.
Figure 79 Dimensional data
Table 27 Liebert XDC dimensions, weight
Air-Cooled
Model Dimensional Data, inches (mm)
Shipping Weight
lb. (kg)
50/60Hz A B * C D E F Domestic Export
XDC160 74 (1880) 34 (864) 33-1/8 (841) 33 (838) 72 (1829) 78 (1981) 1945 (882) 2093 (949)
* Dimension does not include the bezel of the disconnect switch, the handle or the control bezel.
Table 28 Liebert XD Chiller dimensions, weight
Air Cooled Model
Dimensional Data, inches (mm) Shipping Weight, lb (kg)
A B * C D E Domestic Export
Liebert XDC160 74 (1880) 34 (864) 33-1/8 (841) 33 (838) 72 (1829) 1945 (882) 2093 (949)
* Dimension does not include the bezel of the disconnect switch.
C
D
B
Overall
F
Height
of Unit
A
Overall
Shaded areas indicate
a recommended
clearance of 36in (914mm) for
component access.
UNIT DIMENSIONAL DATA
D
Unit Base
E
Unit Base
FLOOR CUTOUT DIMENSIONS
DPN001599
Pg. 2, Rev. 4
Recommended minimum
hot gas supply and liquid
return piping opening
17"
(431.8mm)
5"
(127mm)
1"
(25.4mm)