Technical Specifications

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV
63
4.11 Low-Voltage Wiring—Liebert XDO Smart Modules
Low-voltage connections to the Liebert XDO are available only on smart modules.
Viewing the Liebert XDO from the front or from above, the low-voltage terminal block is on the right
side of the module (see Figure 65). Make low-voltage connections on these modules according to site-
specific drawings. The module must be installed in accordance with national and local wiring regula-
tions.
For Liebert XDO smart modules, the low-voltage connections are on the electric box inside the Liebert
XDO. Knockouts for the low-voltage connections are on the front of the Liebert XDO, near the top (see
Figure 65).
Terminal block connections 37, 38 and 82 through 87 can be connected to a monitoring unit, such as
Liebert SiteScan
®
. The remote shutdown, condensate detection alarm and fan failure alarms operate
independently of each other.
Contacts 37 and 38 are for remote shutdown.
Contacts terminals 82, 83 and 84 are activated by the condensate detection alarm.
T82 is used for normally open contact closure requirements.
T83 is common.
T84 is used when normally closed contact closure is required.
Contacts terminals 85, 86 and 87 are activated by the fan failure alarm.
T85 is for normally open contact closure requirements.
T86 is common.
T87 is used when normally closed contact closure is required. The condensate detection alarm
and the fan failure alarm operate independently of each other.
P66 and P67 are CAN bus ports.
Figure 65 Low-voltage wiring—Liebert XDO smart modules
TOP
Rear
of Liebert
XDO
DPN000771
Rev. 9
Electric Box
(Access is through
hinged fan tray)
Electric Box
Low-Voltage Terminal Block
Condensate Detection,
Remote Shutdown [37,38] and
Alarm Relay Dry Contacts-low
voltage connections [82 thru 87]