Technical Specifications
Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV
63
4.11 Low-Voltage Wiring—Liebert XDO Smart Modules
Low-voltage connections to the Liebert XDO are available only on smart modules.
Viewing the Liebert XDO from the front or from above, the low-voltage terminal block is on the right
side of the module (see Figure 65). Make low-voltage connections on these modules according to site-
specific drawings. The module must be installed in accordance with national and local wiring regula-
tions.
For Liebert XDO smart modules, the low-voltage connections are on the electric box inside the Liebert
XDO. Knockouts for the low-voltage connections are on the front of the Liebert XDO, near the top (see
Figure 65).
Terminal block connections 37, 38 and 82 through 87 can be connected to a monitoring unit, such as
Liebert SiteScan
®
. The remote shutdown, condensate detection alarm and fan failure alarms operate
independently of each other.
• Contacts 37 and 38 are for remote shutdown.
• Contacts terminals 82, 83 and 84 are activated by the condensate detection alarm.
• T82 is used for normally open contact closure requirements.
• T83 is common.
• T84 is used when normally closed contact closure is required.
• Contacts terminals 85, 86 and 87 are activated by the fan failure alarm.
• T85 is for normally open contact closure requirements.
• T86 is common.
• T87 is used when normally closed contact closure is required. The condensate detection alarm
and the fan failure alarm operate independently of each other.
• P66 and P67 are CAN bus ports.
Figure 65 Low-voltage wiring—Liebert XDO smart modules
TOP
Rear
of Liebert
XDO
DPN000771
Rev. 9
Electric Box
(Access is through
hinged fan tray)
Electric Box
Low-Voltage Terminal Block
Condensate Detection,
Remote Shutdown [37,38] and
Alarm Relay Dry Contacts-low
voltage connections [82 thru 87]