4.7 Connecting High-Voltage Wiring—Liebert XDH
The Liebert XDH requires single-phase power for normal operation. The module ships with two power
cords, each 10 feet (3m) long with NEMA 5-15 plugs, which connect to common, three-prong outlets
(see Figures 55 and 56).
Figure 55 Basic Liebert XDH electrical connections
Figure 56 Smart Liebert XDH electrical connections
Rear Door and
Side Panel not
shown for clarity
IEC Primary
and Secondary
Power Inlets
Strain relief points
for power cords
DPN001180
Pg. 4, Rev. 5
60Hz MODELS ONLY
Field-wiring connections
at terminal strip to be NEC
Class 2. Use switch contacts
with 75VA minimum rating.
50Hz MODELS ONLY
Field-wiring connections
at terminal strip for safety extra
low voltage circuits only. Use
switch contacts rated 75VA
minimum, 24VAC maximum.
Condensate Detection,
Remote Shutdown [37,38]
and Alarm Relay Dry
Contacts/Low Voltage
Connections (82 thru 87).