Technical Specifications
Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV
53
4.6 Optional Features—Liebert XDH
• Smart Module—Smart modules will allow remote shutdown, fan failure alarms and
automatically switching the second fan bank On and Off. The controls save energy by permitting
the module to turn one fan in each fan bank Off based on the supply and return temperature.
Liebert XD smart modules are able to provide alarm conditions such as fan failure or condensate
detection at the Liebert XDP display via CANbus communication. For electrical connection
details, refer to the Liebert XDH user manual, SL-17210, available on the Liebert Web site:
www.liebert.com
• Refrigerant Precharge—The Liebert XDH can be precharged with refrigerant. The module will
have one-shot fittings and will be pressurized. The one-shot Liebert XD Flex Piping will also be
precharged with refrigerant.
• Field-Installed Flexible Piping (for use with prefabricated piping assemblies)—Field-installed
flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters).
Connection style to the module end may be straight or 90 degrees with one-shot style couplings or
removable couplings. Flex pipes with one-shot connections will have pressurized R134a. Flex
pipes with removable connections will have a low pressure nitrogen charge Connection to the
prefabricated piping assembly is with a threaded coupler. For information on acquiring the
correct kit for your installation, refer to DPN000780, available by calling 1-800-LIEBERT and
from your local Emerson representative.
• Tie-Down Bracket—An optional tie-down bracket may be installed on the Liebert XDH to
secure it in the row. The bracket keeps space between the Liebert XDH and adjacent equipment
constant, preventing vibration.
Figure 53 Liebert XDH dimensions
FRONT
12" (305mm)
78"
(1981mm)
42
(1067mm)
FRONT
80"
(2032mm)