Technical Specifications
Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV
52
4.4.1 Header System—Liebert XDCF
The Liebert XDCF module system requires use of the Liebert XD prefabricated piping assembly or
port kit. The prefabricated piping is compatible with the flex pipe required to attach to the Liebert
XDCF modules.
Figure 52 Liebert XDCF supply and return piping access points
4.5 Liebert XDH Standard Features
• Dual Refrigeration Circuits—Each Liebert XDH has two refrigeration circuits, one in the
upper half of the module and one in the lower half. Dual refrigeration circuits permit altering
cooling levels in response to server room conditions. The dual refrigeration circuits permits
interlaced connection of two refrigerant sources to enhance system reliability.
• Dual Power Cords and Power Inlets—The Liebert XDH is supplied with two (2) detachable
power cords 10 ft (3m) long that attach to two IEC power inlets on the rear of the module. Each
power cord has a NEMA 5-15P (IEC 320-C14) plug at the opposite end. The dual power cords
allow the module to be powered by two separate power sources. If the secondary power cord is
connected to a UPS, the Liebert XDH’s fans will continue to operate if utility power fails.
• Top Piping Access—The Liebert XDH has supply and return piping access on the top of each
module. Supply piping connection is 1/2" OD copper pipe, and return piping connection is 7/8" OD
copper.
• Corner Stabilizers—A stabilizer in each corner permits rolling the Liebert XDH with greater
ease and less chance of tipping.
• Air Diffusers—Two diffusers, one on the upper half of the module and one on the lower half,
enhance flow of cooling air. Uni-directional and bi-directional diffusers are available.
1-7/16"
(37mm)
3-9/16"
(90mm)
7-5/16"
(186mm)
Supply Pipe
(1/2" diameter)
Return Pipe
(5/8" diameter)
Pipe locations and
dimensions are the
same for upper and
lower modules