Technical Specifications

Designing a Liebert XD Solution
44
3.25 Electrical
Make all wiring and electrical connections in accordance with local and national codes. Refer to the
applicable table in 9.0 - Specifications and Model Number Nomenclature regarding wire size
and circuit protection requirements. Refer to electrical schematic when making connections.
3.26 Temperature/Humidity Sensor Locations
The display panel sensor and Liebert iCOM sensor (shipped loose) must always be installed in the
conditioned space. The display panel sensor and Liebert iCOM sensor may be mounted on the Liebert
XDC/XDP’s front door if the unit is located in the area that it conditions.
The remote temperature / humidity sensor for the Liebert XDP and the Liebert XDC should be
installed in the higher-temperature portion of the cold aisle where the Liebert XD modules are
located. Alternatively, it can be placed on the return air side of the primary air mover, such as a
Liebert DS, in the room if it represents the conditions where all the Liebert XD cooling modules are
located. It should not be installed where ambient air might cause false readings, for example, near
unsealed doors, windows and similar areas.