Technical Specifications
Designing a Liebert XD Solution
43
Figure 41 Piping access points
Chilled water connections to the Liebert XDP are near the bottom of the unit. Refer to the Liebert
XDP user manual (SL-16644) for further information. Piping is routed downward from the unit to
chilled water piping under the raised floor. Connections are made using standard practices for copper
chilled water piping. Field-supplied Victaulic
®
connections may be used to simplify installation in
existing facilities. Refer to Table 75 for additional information.
Table 21 Unit piping outlet connection sizes, inches, OD Cu
Model Pipe Connection Point
50/60 HzABCD
XDP160 2-1/8 1-1/8 2-5/8 2-5/8
Dimensions are
approximate
and subject to change
without notice.
16-1/8"
(409.6mm)
17-1/4"
(438mm)
10" (254mm)
19"
(483mm)
B - Supply to Liebert XD Cooling Modules
D - Chilled Water Return
To Chilled Water Source
C - Chilled Water Supply
From Chilled Water Source
Strainer ***
* Allow 8" (204mm) clearance for filter replacement.
** To ensure ensure all refrigerant flow is filtered,
install the filter dryer assembly between the discharge
line of the Liebert XDP and the first bypass
flow controller or the first Liebert XD cooling module.
*** For each Liebert XDP unit, a separate
20-40 mesh strainer is REQUIRED in the
chilled water supply from the chilled water
source. The strainer is field-supplied and
field-installed. The maximum distance
of the strainer is 10 feet (3m) from the
Liebert XDP.
DPN001598
Pg. 3, Rev. 7
Install replaceable
filter dryer assembly
in liquid supply line B.
To first cooling module
or bypass flow controller **
* Orientation
determined
by installer.
Orientation
determined
by installer *
Orientation
determined
by installer *
To first cooling
module or bypass
flow controller **
Close this
valve during
normal
operation
A - Return from Liebert XD
cooling modules
Emerson recommends field-installation
of shutoff valves at these points to permit
isolating the Liebert XDP for maintenance