Technical Specifications
Designing a Liebert XD Solution
40
Example
A space is 5,000 square feet, with an 18" raised floor and an 8' 6" suspended ceiling. Liebert XDOs
and a Liebert XDP are to be placed in this raised-floor area.
The volume of the space is (1.5 + 8.5) x 5,000 or 50,000 cubic feet.
The maximum amount of R-134a refrigerant that can be used in a single Liebert XDP/Liebert
XDC/Liebert XD module system within this space is 13 * (50000/1000) = 13 * 50 = 650 lb.
Multiple Liebert XD systems can be installed in this space, as long as the amount of R-134a
refrigerant in any one system does not exceed 650lb. (294.8kg).The maximum amount of
refrigerant is 650lb (294.8kg) per Liebert XD loop.
3.23 Determining Refrigerant Volume
After the preliminary system design is completed, Tables 15 through 20 may be used to determine
the amount of refrigerant required. Perform the calculation below for each Liebert XD system being
configured.
3.23.1 Liebert XDP/Liebert XDC Pumped R-134a Circuit Volume
This is the refrigerant circuit from the Liebert XDP/Liebert to the Liebert XD cooling module.
NOTE
Local codes might permit exceeding the maximum refrigerant limit above if a refrigerant
detector and an exhaust system are installed. Installing oxygen sensors may meet some local
codes.
NOTE
All lengths in Tables 15, 16, 17 and 18, are actual pipe lengths, not equivalent pipe lengths.
NOTE
System refrigerant volume calculations in Tables 15, 16, 17 and 18, are based on a fully
loaded system. Additional charge may be required for lightly loaded systems.
Table 15 System R-134a charge for a Liebert XDP/Liebert XDC with any model
Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF
Refrigerant Charge,
lb (kg)
Per Liebert XD Unit
(Excludes Connector Lines to and from Liebert XD Cooling Module)
157 (71.2) Liebert XDP/Liebert XDC
3.55 (1.61) Liebert XDO
2.32 (1.05) Liebert XDV
2.66 (1.21) Liebert XDH (per circuit)
1.41 (0.64) Liebert XDCF
4 (1.81) Liebert XDR
Table 16 System refrigerant charge for the supply and return mains
Refrigerant Charge,
lb/foot (kg/m)
Supply/Return Main Length and Diameter
0.45 (0.67) Main supply actual length per 1-1/8" OD copper tubing
0.68 (1.01) Main supply actual length per 1-3/8" OD copper tubing
0.28 (0.42) Main return actual length per 2-1/8" OD copper tubing
0.43 (0.64) Main return actual length per 2-5/8" OD copper tubing