Technical Specifications

Designing a Liebert XD Solution
15
3.3 Selecting Liebert XD Cooling Modules
The next step is to select the Liebert XD cooling modules to be configured into the solution. Liebert
XD modules that use pumped refrigerant can be connected to the same Liebert XDP/Liebert XDC
piping circuit. This includes the Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and
Liebert XDV.
Generally, the Liebert XDO is selected for use in new installations or renovations where the module
can be installed on the ceiling or in the overhead space.
The Liebert XDV is designed to permit mounting directly on top of an equipment cabinet, for ease of
installation in existing facilities. The Liebert XDV may also be suspended from overhead, using
suitable mounting methods.
The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and
equipment without exhausting heat into the room. Two modules may be mounted on the rear of a
BladeFrame cabinet.
The Liebert XDH is installed among equipment cabinets and is particularly suited for new
installations.
The Liebert XDR replaces the rear door of an equipment cabinet.
Example
Continuing the preceding data center example (in 3.2 - Calculate the Heat Load to be Handled
by Liebert XD System) of a server room 2000 ft
2
with 30 racks (15 producing 20kW of heat per rack
and 15 producing 10 kW of heat per rack), the three Liebert XDPs required can supply coolant to
various types of Liebert XD modules. For instance, the racks with 20kW per rack could be cooled with
either Liebert XDH20, Liebert XDO20 or Liebert XDR20. The racks with 10kW per rack could be
cooled using the Liebert XDV10.
1. For the 15 racks with 20kW of heat each, the total load is:
15 racks x 20kW per rack = 300kW
The perimeter cooling will address the first 2-5kW per rack:
2kW x 15 racks = 30kW
The Liebert XD solution would have to remove 270kW for these racks with higher heat load.
300kW - 30kW = 270kW
2. For the 15 racks with 10kW of heat each, the total load is:
15 racks x 10kW per rack = 150kW
The base cooling will address the first 2-5kW/rack:
2kW x 15 racks = 30kW
The Liebert XD solution would have to remove 120kW for these racks with a higher heat load.
150kW - 30kW = 120kW
3. For this data center example, the Liebert XD solution would consist of:
3 Liebert XDP160s
12 Liebert XDV10s
and any of the following:
13 Liebert XDH20s
12 Liebert XDO20s
15 Liebert XDR20s
Module
Conditions
°F (°C)
Capacity at
Conditions, kW
Load,
kW
Modules
Required
Liebert XDH20 98 (36.6) 22.0 270 13
Liebert XDO20 98 (36.6) 22.5 270 12
Liebert XDR20 98 (36.6) 22.0 270 15
Module
Conditions
°F (°C)
Capacity at
Conditions, kW
Load,
kW
Modules
Required
Liebert XDV10 98 (36.6) 10.0 120 12