Technical Specifications

Specifications and Model Number Nomenclature
162
Figure 141 Liebert XDC model number nomenclature
Table 74 Floor stand specifications—Liebert XDC with 40% ethylene glycol
XDC160 Glycol Floor Stand - 60Hz - 40% EG
189192G3
Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41)
Max Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43)
Performance Data
Cooling capacity, tons (kW) 42.5 (149.4)
Total Heat Rejection, (kW) 192.6
Flow, GPM 204
Pressure Drop, psi (ft water) 35.9 (82.9)
Heat Rejection Equipment
Drycooler DDNT 940A 2 x DDNT 880A*
Drycooler Pressure Drop, psi (ft water) 6.5 (15.1) 2.7 (6.3)
Glycol pump package - 10HP 460V - D10ANTS1317; 208V - D10YNTS1317
Pump Control Package - 208V RP020HY04S0758
Pump Control Package - 460V RP020HA08S0758
Pump Total Head @ 204 GPM, ft water 145
Water regulating valve size 1-1/4"
Piping Connections
Water / glycol supply and return lines 2-5/8"
* When multiple drycoolers are used ensure flow is balanced.
A
Place holder
XD C 160 *
Chiller
unit
Revision
level
Liebert
Xtreme heat
Density system
Place holder
Example: XDC160AA– –*
A
Voltage-phase-frequency
A = 460V-3ph-60Hz
M = 380/415-3ph-50Hz
Place holder
Model size