Technical Specifications

Specifications and Model Number Nomenclature
160
Table 71 Liebert XDC160 specifications
Models
XDC160 Air XDC160 Water / Glycol
XDC160AA XDC160AM
189192G3 (90-100°F)
189192G5 (65-85°F)
Cooling Capacity, tons (kW)
46 (160) 37 (130)
See
Tables 72, 73 and 74 for
Water/Glycol
performance data
Minimum Load 40% of system nominal capacity (64 kW for 60Hz unit)
Electrical Requirements
Input 460V-3ph-60Hz 380/415V-3ph-50Hz 460V-3ph-60Hz
Full Load Amps 79A
Minimum supply wire sizing ampacity 84A
Maximum fuse or circuit breaker size 100A
Dimensions, inches (mm)
Height - Main unit only 78 (1981)
Height - Main unit only, as shipped 83 (2108)
Width - Main unit 74 (1879)
Depth - Main unit 34-5/8 (879)
Height - Water/Glycol-Cooled Condenser Stand N/A 24 (607)
Width - Water/Glycol-Cooled Condenser Stand N/A 72 (1829)
Depth - Water/Glycol-Cooled Condenser Stand N/A 33 (839)
Weight, lb (kg)
Main unit only 1800 (817)
Main unit only, as shipped Domestic: 1945 (882); Export: 2093 (949)
Water/Glycol-Cooled Condenser Stand N/A 1075 (488)
Water/Glycol-Cooled Condenser Stand, as shipped N/A 1150 (521)
Pipe Connections, inches, O.D., Cu
Liebert XD Coolant supply to Liebert XD cooling
modules
1-1/8
Liebert XD Coolant return from Liebert XD cooling
modules
2-1/8
Liquid line, DX circuit 7/8
Hot gas line, DX circuit 1-3/8
Heat Rejection Equipment
95°F (35°C) ambient air-cooled condenser 2-DCSL415 N/A
105°F (41°C) ambient air-cooled condenser 2 -DCSL616 N/A
Number of Liebert XD Cooling Modules Connected, Maximum (Minimum)
Liebert XDCF10 16 (6)
Liebert XDH20 8 (4)
Liebert XDH32 5 (2)
Liebert XDO16 10 (4)
Liebert XDO20 8 (4)
Liebert XDV8 20 (8)
Liebert XDV10 16 (7)
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
Maximum Ambient Operating Temperature °F (°C) 86 (30)
Agency
Approvals CSA CE CSA