Plan wiring runs for Unit-to-Module (U2M) communication when designing the layout of the
conditioned space. In addition to general good wiring practices, take into account:
Keep control and communication cables away from power cables to prevent electromagnetic
interference.
Do not bend cables to less than four times the diameter of the cable.
Do not deform cables when securing in bundles or when hanging them.
Keep cables away from devices that can introduce noise into them, such as machines,
fluorescentlights, and electronics.
Avoid stretching cables-tension when pulling cables should not exceed 25 pounds (11kg).
Do not secure cables with any method that might damage them; use approved hangers, such as
those used for telephone wire and RG-6 coaxial wire; available at most hardware stores.
Do not run cables through conduit. Cables should be treated the same as any other data cable.
Running CANbus cables through conduit will increase the total length required.