Technical Specifications
Heat Rejection
98
Table 34 Condenser weights and connections
Outdoor
Ambient
°F (°C)
Model
50/60Hz
Number
of Fans
Connection
Size, OD, In.
Net Weight
lb (kg) Receiver Part #
Receivers
per
Condenser
Net
Weight
lb (kg)Hot Gas Liquid
-30 to 100
(-34 to 38)
DCSL415 4 1-3/8 1-1/8 840 (381) 185010G2
1
/ G4
2
1 260 (118)
-30 to 105
(-34 to 41)
DCSL616 6 (2) 1-5/8 (2) 1-1/8 1380 (626) 179713G1
1
/ G2
2
1 424 (192)
35 to 105
(-34 to 41)
DCSL616 6 (2) 1-5/8 (2) 1-1/8 1380 (626) 181610G2
1
/ G4
2
1200 (91)
1. 120V
2. 230V
Table 35 60Hz electrical condenser data—Liebert Lee-Temp controlled/fan-cycling
Model # 083, 104, 28K 165, 205, 60K 251, 308, 90K 415, 510 616 830, 1010
# of Fans 1 2 3 4 6 8
Input
Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
208/230
3
3.5 4.4 15 7.0 7.9 15 10.5 11.4 15 14.0 14.9 20 21.0 21.9 25 28.0 28.9 35
460 1.7 2.1 15 3.4 3.8 15 5.1 5.5 15 6.8 7.2 15 10.2 10.6 15 13.6 14.0 20
575 1.4 1.8 15 2.8 3.2 15 4.2 4.6 15 5.6 6.0 15 8.4 8.8 15 11.2 11.6 15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device
Table 36 50Hz condenser full load amp values
Condenser
Control Type
Liebert Lee Temp
Controlled/Fan-Cycling
Model # # of Fans
Input Voltage - Phase
200/230-3 380/415-3
415 4 14.0 6.8
616 6 21.0 10.2
Table 37 Liebert Lee-Temp receiver electrical data, 50Hz and 60Hz
Rated Voltage - Single Phase 120 200/208/230
Watts/Receiver 150 300 450 150 300 450
Full Load Amps 1.4 2.8 4.2 0.7 1.4 2.1
Wire Size Amps 1.8 3.5 5.3 0.9 1.8 2.7
Maximum Overcurrent
Protection Device, Amps
15 15 15 15 15 15
The Liebert Lee-Temp receiver requires a separate power feed for heaters. The condenser is not designed to supply power to the receiver.