Technical Specifications
Heat Rejection
96
6.1.5 Propeller Fan
Aluminum propeller fan blades are secured to a corrosion-protected steel hub. Fan guards are heavy
gauge, close-meshed steel wire with corrosion resistant PVC finish rated to pass a 675-hour salt spray
test. Fans are secured to the fan motor shaft by a keyed hub and dual setscrews. Fan diameter is
26" (660mm) or less. The fans are factory-balanced and run before shipment.
6.1.6 Fan Motor
The condenser's fan motor is a continuous air-over design equipped with rain shield and permanently
sealed bearing. Die-formed, galvanized steel supports are used for rigid mounting of the motor.
6.1.7 Electrical Controls
Electrical controls, overload protection devices and service connection terminals are factory-wired
inside the integral electrical panel section of the housing. A locking disconnect switch is
factory-mounted and wired to the electrical panel and controlled via an externally mounted locking
door handle. An indoor unit interlock circuit enables condenser operation whenever indoor unit
compressors are active. Only supply wiring and indoor unit interlock wiring are required at condenser
installation.
6.2 Mechanical Considerations
6.2.1 Dimensions
Figure 99 Condenser planning dimensional data—Four-fan units
Note:
Overall height to the top of fan guard
43-1/8" (1095mm)
Eyebolts
for Lifting
37-7/8"
(962mm)
171-1/2"
(4356mm)
70"
(1778mm)
164"
(4166mm)
43-3/16"
(1097mm)
43-9/16"
(1106mm)
18"
(457mm)
See Figure 101 for typical
condenser footprint dimensions.
41-3/16"
(1046 mm)
82" (2083mm )
80"
(2032mm)
Four-Fan
Condenser
Legs supplied with
Liebert Lee -Temp
option only
42"
(1067 mm)
Electric
Box
End
ANCHOR PLAN
Emerson recommends a
clearance of 36" (915mm) on
each side for proper operation