Operating instructions
8 Installation
1.1.5 Floor Pedestal Installation
Floor pedestals are optional equipment intended to provide bottom cable clearance without rely-
ing on a raised floor to support the unit. The pedestals are adjustable over a limited range
(approximately 3 1/2 in. [89 mm]) to allow leveling of the unit and minor adjustments of the
installed height.
If floor pedestals are used for the Precision Power Center, additional floor pedestals are required
for the Static Switch.
To install the pedestals, insert the pedestal shaft into the tubing provided in the unit’s base.
Adjust the unit height by turning the welded nut/shaft assembly into or out of the pedestal base.
Lock the height by tightening the jam nut against the pedestal base.
The pedestal may be mounted to the floor by means of the four holes provided in the pedestal
base.
Figure 6 Floor Pedestal Details
NOTE
The floor pedestals may be reverse assembled for shipping. Before
installing the pedestals, be sure they are assembled as shown in Figure 6.
When the pedestal is properly assembled, the washer on the top provides a
bearing surface for the unit, the welded nut provides a means to raise and
lower the height, and the jam nut provides a means to lock the height of the
pedestal.