Operating instructions
38 Installation Drawings
Figure 20 Circuit Breaker Schedule
STATICSWITCH2/BRKTABLEALL/PS214000
10/24/02
PS214000
CIRCUIT BREAKER SCHEDULE
100AMP TO 1000AMP
STATIC TRANSFER SWITCH 2
NOTES:
1. MOLDED CASE BREAKERS ARE 3 POLE, 600VAC RATED. NSF AND NSJ TYPE ARE AUTOMATIC
MOLDED CASE BREAKERS WHICH HAVE MAGNETIC TRIP ONLY. THE CK TYPE ARE NON-
AUTOMATIC MOLDED CASE BREAKERS WHICH HAVE NO THERMAL OR MAGNETIC TRIP.
2. UPSTREAM DEVICES (BY OTHERS) MUST PROVIDE OVERCURRENT PROTECTION. UPSTREAM
OVERCURRENT PROTECTION SHOULD HAVE AMPACITY EQUAL TO OR LESS THAN THE AMPERE
RATING OF THE STATIC SWITCH MOLDED CASE BREAKER. TO MEET THE WITHSTAND RATING
LISTED, CK TYPE MOLDED CASE BREAKER MUST BE PROTECTED UPSTREAM BY MERLIN GERIN
CK1200HH CIRCUIT BREAKER.
VOLTAGE
STATIC TRANSFER SWITCH 2, MOLDED CASE BREAKER SCHEDULE
STS2
RATING
AMPACITYVENDOR TYPE
NSF
MERLIN GERIN
WITHSTAND
CURRENT
MERLIN GERIN
MERLIN GERIN
NSF
NSJ
NSJ
CK
CK
MERLIN GERIN
MERLIN GERIN
MERLIN GERIN
DATE
FILE NAME:
COLUMBUS, OHIO 43229
1050 DEARBORN DRIVE,
REV. NO.
DWG. NO.
V CARMONA
REF. DWG.
CHK BY
DRAWN BY